Installation Notes; Figure 1: Correct Wiring Of Neutral Conductors - Siemens LME39 Series Basic Documentation

Gas burner controls
Hide thumbs Also See for LME39 Series:
Table of Contents

Advertisement

Recommendation:
8/73
Building Technologies Division
1.4

Installation notes

 Always run the high voltage ignition cables separate from the unit and other cables
while observing the greatest possible distance
 Do not mix up live and neutral conductors
 Install switches, fuses and earthing, in compliance with local regulations
 The connection diagrams show the burner controls with earthed neutral conductor.
In networks with nonearthed neutral conductor and ionization current supervision,
terminal 2 must be connected to the earth conductor via an RC unit (product no.
ARC 4 668 9066 0). It must be made certain that local regulations are complied with
(e.g. protection against electric shock hazard) since AC 120 V (50/60 Hz) or AC 230 V
(50/60 Hz) mains voltage produces peak leakage currents of 2.7 mA
 Make certain that the maximum permissible current rating of the connection terminals
will not be exceeded
 Do not feed external mains voltage to the control outputs of the unit. When testing the
devices controlled by the burner control (fuel valves, etc.), the burner control must not
be connected
 Check the connecting lines of the air pressure switch for short-circuits (air pressure
switch between terminals 2 and 6). If this is not observed, there is a risk of loss of
safety functions
 To prevent mixup of different types of burner controls, the LME39... must always be
used in connection with grey plug-in bases AGK11.6. Make absolutely certain that
the live conductor for the control thermostat or pressurestat is tapped after the gas
pressure switch and the safety limit thermostat to be connected to terminal 11 (refer
to Connection diagram)
 For safety reasons, feed the neutral conductor to terminal 2. Connect the burner
components (fan, ignition transformer and fuel valves) to the neutral distributor as
shown below in the figure. The connection between neutral conductor and terminal 2
is prewired in the base
Example
Z
M
N

Figure 1: Correct wiring of neutral conductors!

Note!
In extremely EMC-stressed environments, burners without fan motor or burners
equipped with fan control via auxiliary contactor should use an AGK25 to produce a
burden on terminal 3. If not observed, the burner is not reliably started up
Basic Documentation LME39...
1 Safety notes
Legend
V...
Fuel valve
M
Fan motor
Z
Ignition transformer
CC1P7106en
03.02.2016