Blower Speed Control; Burner Assembly - A.O. Smith Cyclone XL 100 Series Service Handbook

Commercial gas water heaters
Table of Contents

Advertisement

The CCB monitors a feedback signal from a sensor that is installed on the blower. The CCB interprets the pulse signal from the sensor
and then sends a signal to the blower to produce the proper blower speed and input.
These models are capable of modulating their input rate. Therefore, the RPM readings can be in between the Heating Speed and
Minimum Modulation Speed RPMs. The input rate should be verified with the water heater operating at full input rate.
Table 2 and Table 3 list the RPMs for each model at high heating speed, low fire speed, and ignition speed.
Nateral Gas
BTHS 750
BTHS 1000
* Note: ±10% High Heating Speed RPMs are based from the Nominal "Certification" Heating Speed RPMs.
Propane Gas
BTHS 750
BTHS 1000
* Note: ±10% High Heating Speed RPMs are based from the Nominal "Certification" Heating Speed RPMs.
The Burner is a radial design burner with a steel fiber jacket on the outer surface and is part of a larger Burner Assembly. Figures below
show side views of the complete Burner Assembly removed from the water heater with key components identified. See the exploded
view in Figure 4 (page 7) also.

BLOWER SPEED CONTROL

BLOWER SPEED CONTROL
Table 2. Blower RPMs - Nateral Gas
Hirh Heatinr Speed - RPM
4475
6000
Table 3. Blower RPMs - Propane Gas
Hirh Heatinr Speed - RPM
4350
5800

BURNER ASSEMBLY

BURNER ASSEMBLY
Flame rod, ½" to
burner surface
Firere 20. Berner Assembly
Low Fire Speed RPM
2300
2300
Low Fire Speed RPM
2700
2700
Spark igniter,
0.125" spark gap,
~1/2" to burner
surface
30
Irnition Speed RPM
2000
2000
Irnition Speed RPM
2000
2000