Charging Levels - Trane Odyssey TTA0724 A Series Installation, Operation And Maintenance Manual

Split system air conditioners odyssey with symbio controls
Hide thumbs Also See for Odyssey TTA0724 A Series:
Table of Contents

Advertisement

I I n n s s t t a a l l l l a a t t i i o o n n

Charging Levels

I I m m p p o o r r t t a a n n t t : : For the correct line diameter, for line
lengths greater than 25 feet, see the
Table 6. Estimated charge levels at AHRI rated line lengths (25 feet) - 50 & 60 Hz
Matched Set
TTA0604DA w/ TWE0764DA
TTA0604DD w/ TWE0724DB
TTA0724*A w/ TWE0904*A
TTA0724*D w/ TWE0724*B
TTA0764DA w/ TWE0764DA
TTA0764DA w/ TWE1014DA
TTA0764DD w/ TWE0764DB
TTA0904*A w/ TWE0904*A
TTA0904*A w/ TWE1204*A
TTA0904*D w/ TWE0904*B
TTA1014DD w/ TWE1014DB
TTA1014DC w/ TWE1014DA
TTA1204*D w/ TWE1204*B
TTA1204*C w/ TWE1204*A
TTA1264DD w/ TWE1264DB
TTA1504*D w/ TWE1504*B
TTA1564DD w/ TWE1564DB
TTA1564DD w/ TWE2014DB
TTA1564DC w/ TWE1564DB
TTA1804*D w/ TWE1804*B
TTA1804*D w/ TWE2404*B
TTA1804*C w/ TWE1804*B
TTA2014DD w/ TWE2014DB
TTA2014DC w/ TWE2014DB
TTA2404*D w/ TWE2404*B
TTA2404*C w/ TWE2404*B
TTA2514DC w/ TWE2514DB
TTA3004*C w/ TWE3004*B
Notes:
1.
For line lengths other than 25', please refer to the Application Guide (SS-APG008*-EN) for charge levels, oil addition and line sizes.
2.
TTA0604DA and TTA0724*A need a reducer for vapor line. (1.375 to 1.125 inch) (1 3/8" to 1 1/8").
3.
TTA2514DC and TTA3004*C are provided with a transition tube to be installed outside of the unit for front or rear access, (1.625 to
2.125 inch) (1 5/8" to 2 1/8"). See Refrigerant Charging Procedure for transition tube location and electrical connections.
26
Refrigerant Charge
Circuit 1
Circuit 2
10.0
N/A
7.0
7.0
N/A
10.0
7.0
7.0
9.7
N/A
N/A
9.5
7.3
7.3
N/A
9.7
9.5
N/A
7.3
7.3
7.6
7.6
N/A
13.1
8.2
8.4
N/A
13.1
9.7
9.7
9.8
9.8
11.5
11.5
9.2
9.4
N/A
21.4
11.5
11.5
9.2
9.3
N/A
22.5
11.6
12.3
N/A
23.8
11.2
11.2
N/A
23.8
N/A
29.8
N/A
29.8
Odyssey Application Guide (SS-APG008*-
EN) available through e-Library or your
local sales office.
Per Circuit
Liquid Line Diameter
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.5 (1/2")
0.625 (5/8")
0.5 (1/2")
0.5 (1/2")
0.625 (5/8")
0.5 (1/2")
0.625 (5/8")
0.5 (1/2")
0.625 (5/8")
0.625 (5/8")
0.625 (5/8")
Vapor Line Diameter
1.125 (1 1/8")
0.875 (7/8")
1.125 (1 1/8")
0.875 (7/8")
1.375 (1 3/8")
1.375 (1 3/8")
1.125 (1 1/8")
1.375 (1 3/8")
1.375 (1 3/8")
1.125 (1 1/8")
1.125 (1 1/8")
1.375 (1 3/8")
1.125 (1 1/8")
1.375 (1 3/8")
1.125 (1 1/8")
1.125 (1 1/8")
1.375 (1 3/8")
1.375 (1 3/8")
1.625 (1 5/8")
1.375 (1 3/8")
1.375 (1 3/8")
1.625 (1 5/8")
1.375 (1 3/8")
1.625 (1 5/8")
1.375 (1 3/8")
1.625 (1 5/8")
2.125 (2 1/8")
2.125 (2 1/8")
SS-SVX001A-EN