Completing The Installation And Commissioning; Charging Refrigerant - Samsung RD VHXF Series Installation Manual

Table of Contents

Advertisement

completing the installation and
commissioning

CHARGING REFRIGERANT

Service valve work for gas pipe
• Block the cap of the service valve after charging the refrigerant.
- Connection torque of the cap for the refrigerant charging port : 6.0N·m(4.425 lbf·ft)
- Connection torque of the stem : 25N·m(18.439 lbf·ft).
- Adjustable torque of the valve stem.
ø19.05(3/4˝)~ : 10.0N·m(7.375 lbf·ft)
When installing 1 outdoor unit
R410A
Scale

46_ completing the installation and commissioning

Cap for the valve stem
Cap for the refrigerant
charging port
Outdoor unit
Liquid side
Gas side
Gauge manifold
Service valve
Vacuum pump

Hide quick links: