Key Function - Samsung RD VHXF Series Installation Manual

Table of Contents

Advertisement

Key function

��
��
��
��
K1
Push 1
time
Refrigerant charging in heating operation
st
Push 2
time
Test run in heating mode
nd
Push 3
time
Pump out operation in heating mode (Outdoor unit's address : NO 1)
rd
Push 4
th
time
Pump out operation in heating mode (Outdoor unit's address : NO 2)
Push 5
time
Pump out operation in heating mode (Outdoor unit's address : NO 3)
th
Push 6
time
Pump out operation in heating mode (Outdoor unit's address : NO 4)
th
Push 7
time
Open all valve of outdoor unit for vacuum preparation (Outdoor unit's address : NO 1)
th
Push 8
time
Open all valve of outdoor unit for vacuum preparation (Outdoor unit's address : NO 2)
th
Push 9
time
Open all valve of outdoor unit for vacuum preparation (Outdoor unit's address : NO 3)
th
Push 10
time
Open all valve of outdoor unit for vacuum preparation (Outdoor unit's address : NO 4)
th
Push 11
time
Open all valve for vacuum preparation (Total outdoor units, indoor unit and MCU units)
th
Push 12
th
time
Return to normal view mode
K2
Push 1
time
Refrigerant charging in cooling operation
st
Push 2
time
Test run in cooling mode
nd
Push 3
time
Pump down operation in cooling mode (All outdoor units)
rd
Push 4
th
time
Pipe checking (Check whether the pipe line of MCU correspond with indoor unit's address in HR system)
Push 5
time
Judgment system of refrigerant amount
th
Push 6
time
Return to normal view mode
th
K3
Push 1
time
Reset
st
K4
Outdoor capacity
Push 1
time
st
Push 2
time
Digital comp loading time
nd
Push 3
time
High pressure (kg/cm
rd
Push 4
time
Low pressure (kg/cm
th
Push 5
time
Discharge temperature of compressor 1
th
Push 6
th
time
Discharge temperature of compressor 2
Push 7
time
Discharge temperature of compressor 3
th
Push 8
time
CT sensor value of compressor 1
th
Push 9
time
CT sensor value of compressor 2
th
Push 10
time
CT sensor value of compressor 3
th
Push 11
time
Suction temperature
th
Push 12
time
Cond_out temperature
th
Push 13
time
Liquid tube temperature
th
Push 14
th
time
Oil temperature sensor on oil balancing pipe
Push 15
time
Sump temperature of compressor 1
th
Push 16
time
Ambient air temperature
th
Push 17
time
EVI_in temperature
th
Push 18
time
EVI_out temperature
th
Push 19
th
time
Main EEV1 step
Push 20
time
Main EEV2 step
th
Push 21
time
EVI EEV step
th
Push 22
th
time
HR EEV step
Push 23
time
Fan step ( SSR or BLDC )
th
Push 24
time
Version
th
Above functions are activated by PCB of "main unit" only.
Key function
Key function
Key function
Key function
)
2
)
2
completing the installation and commissioning _49
Display LED
"K" "1"
"BLANK"
"BLANK"
"K" "2"
"BLANK"
"BLANK"
"K" "3"
"BLANK"
"1"
"K" "3"
"BLANK"
"2"
"K" "3"
"BLANK"
"3"
"K" "3"
"BLANK"
"4"
"K" "4"
"BLANK"
"1"
"K" "4"
"BLANK"
"2"
"K" "4"
"BLANK"
"3"
"K" "4"
"BLANK"
"4"
"K" "4"
"BLANK"
"A"
-
Display LED
"K" "5"
"BLANK"
"BLANK"
"K" "6"
"BLANK"
"BLANK"
"K" "7"
"BLANK"
"BLANK"
"K" "8"
"BLANK"
"BLANK"
"K" "9"
"BLANK"
"BLANK"
Display LED
Display LED
SEG 1
SEG 2, 3, 4
7.5 HP  Off, 0, 8
1
10 HP  Off, 1, 0
12.5HP  Off, 1, 2
2
Ex) Loading 13 sec  Off, 1, 3
3
Ex) High pressure 15.2 (kg/cm
)  1, 5, 2
2
4
Ex) Low pressure 4.3 (kg/cm
)  0, 4, 3
2
5
Ex) 87˚C  0, 8, 7
6
Ex) 87˚C  0, 8, 7
7
Ex) 87˚C  0, 8, 7
8
Ex) 2A  0, 0, 2
9
Ex) 2A  0, 0, 2
A
Ex) 2A  0, 0, 2
B
Ex) -5 ˚C  -, 0, 5
C
Ex) 35˚C  0, 3, 5
C
Ex) 35˚C  0, 3, 5
C
Ex) 35˚C  0, 3, 5
F
Ex) 35˚C  0, 3, 5
G
Ex) 35˚C  0, 3, 5
H
Ex) 35˚C  0, 3, 5
I
Ex) 35˚C  0, 3, 5
J
Ex) 2000 steps  2, 0, 0
K
Ex) 2000 steps  2, 0, 0
L
Ex) 300 steps  3, 0, 0
M
Ex) 300 steps  3, 0, 0
N
Ex) 13 steps  Off, 1, 3