Indoor Unit Setting

1.
Before installing the indoor unit, assign an address to the
indoor unit according to the air conditioning system plan.
2.
The address of the indoor unit is assigned by adjusting
MAIN(SW01, SW02) and RMC(SW03, SW04) rotary switches.
SW01
SW02
SW03
SW04
SW05
SW06
Setting MAIN Address
 The MAIN address is for communication between the
indoor unit and the outdoor unit. Therefore, you must
set it to operate the air conditioner properly.
 You can set the MAIN address from '00' to '99' by mixing
SW01 and SW02.
The MAIN address from '00' to '99' should differ from
each other.
 Check the indoor unit address on the plan that you are
to install and set the address according to the plan.
Note
You may not need to set MAIN address if you
selected Auto Address Setting from the outdoor
unit: see details on the outdoor unit installation
manual.
For Example
When MAIN address is set as "12".
Setting RMC Address
 The SW03, SW04 RMC switch is the address setting
switch for controlling the indoor unit with the centralized
controller.
 You must set the SW03, SW04 and K2 switch when using
the centralized controller.
For Example
When RMC address is set as "12".
SW03
36_ installing your air conditioner
ND£ª£ª£ªQHX£ª£ª _IB IM_32063A_E.indd 36
Cover PCB
SW07
SW04

Additional Functions

�� �� �� ��
����
No.
Function
K1
External room sensor
K2
Centralized controller
SW05
K3
-
K4
-
K1 OFF
Heating mode : Setting temperature compensation
value = 0°C
Thermo OFF  Fan OFF
�� �� �� ��
����
No.
Function
K5
Heating Current Temperature Compensation
K6
Filter Time
SW06
K7
-
K8
-
�� ��� ��� ���
����
No.
Function
Indoor Expansion Valve
K9
For Heating Stop
Wired Remocon Group
SW07
K10
Master
K11
External control
K12
Operation output
ON
OFF
Not use
Use
Not use
Use
-
-
-
-
ON
OFF
+2°C
+5°C
1,000
2,000
hours
hours
-
-
-
-
ON
OFF
80 or 160 step
80 or 160 step
(80 step last for at
least 1 hour)
Not Use
Use
Not Use
Use
Thermal ON
Operation ON
2010-4-24 8:54:15