1.
Connecting the power supply
The unit can use AC power sources between 100 and 240 Volts.
Connect the power supply to a nearby socket and the DC connector to the DC supply plug (Fig. 3-2)
Connect the ground line securely to (1)
Please do not connect the power supply until all other wiring is finished and the box is closed
2.
Connecting the communication lines
Use the field supplied 3 pieces minimum 5 x 0,5 mm² wires to connect each PAW-T10 (contacts 2, 3, 8,
11, 12 unit 1 / contacts 4, 5, 9, 13, 14 unit 2 / contacts 6, 7, 10, 15, 16 unit 3 (optional) )
Preferrably route the wires through the pre-cut holes in the bottom part, you may however choose any
other of the pre-cut holes on the right side or the top. Please use the supplied M20 cable bushings.
Even insertion by the backside is possible, however it may be difficult to run the wires then through the
box under the internal mounting plate.
The communication wires shouldn't exceed 10 m. In case you need a longer distance, please choose a
bigger wiring diameter.
Do not run the communication lines through the same conduit as any local power supply cable or run
close to any power supply line (maintain at least 30 cm separation).
On each PAW-T10 bridge the contacts 7 & 10 by using the 1 x 0,5 mm² wire.
Optional you can connect the all alarm signal (contacts 19 & 20) to external BMS (max. 250 VAC 2A or
30 VDC 2A)
Optional you can connect the all operation signal (contacts 17 & 18) to external BMS (max. 30 VDC 1 A
or 110 VDC 0,3 A)

Basic Wiring Diagram

1
2
3
4
5
Unit or Group 1
6
7
8
9
10
Unit or Group 2
11
12
13
14
15
16
17
18
19
20
All Operation All Alarm