Troubleshooting Guide
Error
Error Type
No.
01
Indoor unit air sensor error
02
Indoor unit pipe inlet sensor error
06
Indoor unit pipe outlet sensor error
n Error diagnosis and countermeasure flow chart
Is sensor properly
connected to PCB?
Yes
Is the resistance value
of sensor normal?*
Yes
Change the PCB
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) ' Normal
Air temp sensor: 10°C = 20.7kΩ : 25°C= 10kΩ : 50°C= 3.4kΩ
Pipe temp sensor: 10°C = 10kΩ
Indoor unit sensor is
No
Connect properly to PCB
No
Change the sensor
: 25°C= 5kΩ : 50°C= 1.8kΩ
- 52 -
Error Point
1. Indoor unit PCB wrong connection
2. Indoor unit PCB failure
open/short
3. Sensor problem (main reason)
CN-ROOM : Indoor air temp sensor
CN-PIPE IN : Pipe inlet temp sensor
CN-PIPE OUT : Pipe outlet temp sensor
Measure the resistance of outlet pipe temp sensor.
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
Main Reasons