Bradford White EFTM Installation & Operating Manual page 19

Ultra high efficiency commercial gas water heater
Table of Contents

Advertisement

Internet Version for Reference Only
Figure 12a. Vent Terminal Clearances (Other than Direct Vent or "Power Vented" Installations)
A=
Clearance above
grade, veranda,
porch, deck or
balcony
B=
Clearance to widow
or door that may be
opened
C=
Clearance to
permanently closed
widow
D=
Vertical clearance to
ventilated soffit
located above the
terminal within a
horizontal distance of
2 feet (61 cm) from
the center line of the
terminal
E=
Clearance to
unventilated soffit
F=
Clearance to outside
corner
G=
Clearance to inside
corner
1
In accordance with the current CAN/CGA-B149 Installation Codes.
2
In accordance with the current ANSI Z223.1-(Latest Edition)/NFPA 54 National Fuel Gas Code.
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family
dwellings and serves both dwellings.
Permitted only if a veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
*a) A minimum clearance value determined by testing in accordance with section 2.20.
*b) "Clearance in accordance with local installation codes and the requirements of the gas supplier".
2
Canadian
US Installations
1
Installations
12 inches
12 inches
(30 cm)
(30 cm)
36 inches
4 feet (1.2 m)
(91 cm)
below or to the
side of opening;
12 inches (30
cm) above
opening
*b
*b
*b
*b
*b
*b
*b
*b
36 inches
36 inches
(91 cm)*a
(91 cm)*a
H=
Clearance to each side
of center line extended
above meter/regulator
assembly
I=
Clearance to service
regulator vent outlet or
oil tank vent
J=
Clearance to non-
mechanical air supply
inlet to building or the
combustion air inlet to
any other appliance
K=
Clearance to a
mechanical air supply
inlet
L=
Clearance above paved
sidewalk or paved
driveway located on
public property
M=
Clearance under a
veranda, porch, deck, or
balcony
19
Canadian
US Installations
1
Installations
3 feet (91 cm) within a
height 15 feet (4.6 m)
above the
meter/regulator
assembly
36 inches
(91 cm)
36 inches
4 feet (1.2m)
(91 cm)
below or to side
of opening; 12
inches (30 cm)
above opening.
6 feet
3 feet (91 cm)
(1.83 m)
above if within
10 feet
horizontally
7 feet
7 feet
(2.13 m)†
(2.13 m)†
12 inches (30 cm) ‡
2
*b
*b
*b