Siemens 7UG0571-1FT20 Operating Instructions Manual page 6

Automatic power factor controller relay

Advertisement

Modbus Register Addresses List
Readable parameters: [
For Measuring
He x
Address
Parameter
Address
Voltage V1N
30000
0x00
30002
0x02
Voltage V2N
Voltage V3N
30004
0x04
Average Voltage LN
30006
0x06
Voltage V12
30008
0x08
Voltage V23
30010
0x0A
Voltage V31
30012
0x0C
Average Voltage LL
30014
0x0E
30016
0x10
Current I1
30018
0x12
Current I2
30020
0x14
Current I3
Average Current
30022
0x16
30024
0x18
kW1
30026
0x1A
kW2
30028
0x1C
kW3
30030
0x1E
kVA1
30032
0x20
kVA2
30034
0x22
kVA3
30036
0x24
kVAr1
30038
0x26
kVAr2
30040
0x28
kVAr3
30042
Total kW
0x2A
30044
0x2C
Total kVA
Readable / writable parameters:
He x
Address
Parameter
Address
40000
0x00
Password-1
Min value:0
Value
40001
0x01
N/W selection
0
1
2
3
Min value Max value
CT Secondary (A)
40002
0x02
1
CT primary
(A)
40003
0x03
5
(CT Secondary=5)
CT primary
(A)
1
(CT Secondary=1)
PT Secondary (V)
40004
0x04
100
PT primary (V)
40005
0x05
100
40007
0x07
Slave id
1
Value
Baud rate (bps)
40008
0x08
0x0000
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
Parity
40009
0x09
0x0000
0x0001
0x0002
Stop bit
40010
0x0A
0x0000
0x0001
40011
0x0B
Backlight OFF
(Sec.)
0
Factory Default
40012
0x0C
1
40013
0x0D
Reset kWh
1
40014
0x0E
Reset kVAh
1
40015
0x0F
Reset kVArh
1
Min value
40016
0x10
Password-2
0
Phase
0-0, 1-90, 2-120, 3-210, 4-240, 5-330
40017
0x11
Compensation ( )
0
*
13 & 14th relay will be used for control switching only when customer selects 14 relay in config. else for FAN & ALM respectively.
6
: Length (Register) : 2; Data structure : Float,
He x
Address
Parameter
Address
30046
0x2E
Total kVAr
30048
0x30
PF1
30050
0x32
PF2
30052
0x34
PF3
Average PF
30054
0x36
Frequency
30056
0x38
30058
0x3A
kWh
30060
0x3C
kVAh
30062
0x3E
kVArh
Temperature
30064
0x40
No Voltage Error
30066
0x42
Under Voltage Error
30067
0x43
Over Voltage Error
30068
0x44
30069
0x45
THD I Error
Temperature Error
30070
0x46
Over compensate Error
30071
0x47
Under compensate Error
30072
0x48
30073
0x49
CT Error
Note : For Error 0 :No Error ; 1 :Error Present
30074
0x4A-
Relay1-Relay12/14* Status
-30087
0x57
Digital Input Status
30088
0x58
Note: For Status 0:OFF;1:ON
Length
Range
(Register)
Max value : 9998
1
Meaning
3P4W
1
3P3W
1
1P2W
1
2P2W
1
5
1
5 - 9999
1
1 - 9999
500
1
500000
2
255
1
Meaning
300
1
600
1200
2400
4800
9600
19200
None
1
Odd
Even
1
1
2
7200
1
Set to factory setting range
1
Reset Total Active Energy
1
Reset Total Apparent Energy
1
Reset Total Reactive Energy
1
Max value
9998
1
1
For Error
: Length (Register) : 1; Data structure: Integer]
He x
Address
Parameter
Address
30090-
0x5A -
Bank1 - Bank 12/14* Value
30116
0x74
Total Harmonic Distortion(THD)
THD of Voltage V1N
30124
0x7C
30126
0x7E
THD of Voltage V2N
THD of Voltage V3N
30128
0x80
THD of Voltage V12
30130
0x82
THD of Voltage V23
30132
0x84
THD of Voltage V31
30134
0x86
30136
0x88
THD of Current I1
30138
0x8A
THD of Current I2
30140
0x8C
THD of Current I3
30684
0x2AC
Serial number in HEX
Formula to nd address of individual Harmonic
Constant Parameter
0
1
2
3
4
5
6
7
8
He x
Dat a
Address
Parameter
Structure
Address
Integer
Nominal Voltage(V)
40018
0x12
Threshold
40019
0x13
Voltage
Integer
40020
0x14
Auto Initialization
Integer
Relay Count
40021
0x15
Integer
40022
0x16
Control Mode
Integer
40023
0x17
Switching Program
Target Power
40024
0x18
Integer
Factor (PF)
Step time (Sec.)
40025
0x19
Integer
Discharge
40026
0x1A
Time(Sec.)
Control
40027
0x1B
Sensitivity(%)
Integer
No Voltage
40028
0x1C
Integer
40029
0x1D
Over Voltage
Integer
Set
Over
40030
0x1E
Voltage
Integer
40031
Under Voltage
0x1F
Set Under
40032
0x20
Voltage(V)
40033
0x21
THDI
40034
THDI Range(%)
0x22
Over
40035
0x23
Compensation
Under
40036
0x24
Compensation
Integer
Step Error
40037
0x25
Set Step Error(%)
40038
0x26
CT Polarity error
40039
0x27
Integer
Over Temperature
40040
0x28
Set Over
40041
0x29
Temperature ( C)
Integer
Fan Settings
40042
0x2A
Integer
Hysteresis
40043
0x2B
Integer
V
oltage
Integer
Hysteresis PF(%)
0x2C
40044
0x2D-
Integer
40045 -
Relay1-Relay14
0X3A
40058
Trip time setting
40059
0x3B
Integer
Low Current
40060
0x3C
setting(%)
Integer
{142 + [(Harmonic no-2) x 2] + 60 x
Constant Parameter }
For Example,
To find the 14 Harmonic address of
th
Voltage V31 following formula can be used:
Formula with the parameter :
{142 + [(Harmonic no-2) x 2] + 60 x C P}
Eg. {142 + [(14-2) x 2 ] + 60 x 5} = 466
So, Check the 14 Harmonic of Voltage V31
at 466 address.
Read Coil Status
Hex
Address
Address
00000-
0x00-
0x0D
00013
Force Single Coil:
Hex
Address
Address
00000-
0x00-
Meaning
0x0D
00013
Voltage V1N
Voltage V2N
Voltage V3N
Voltage V12
Voltage V23
Voltage V31
Current I1
Current I2
Current I3
Range
50
50 - 440
0
0 - 100
(%)
0 : NO ; 1 : YES
1
12 / 14*
8/12/14*
0 - MANUAL ; 1 - AUTO
0 - Auto ; 1 - Rotation ; 2 - Linear
800
-800
1
1-999
1
1-9999
55
55 - 100
0 : OFF ; 1 : ON
0 : OFF ; 1 : ON
50 - 277V (L-N); 85 - 480V (L-L)
(V)
0 : OFF ; 1 : ON
50 - 240V (L-N); 85 - 415V (L-L)
0 : OFF ; 1 : ON
20 - 100
20
0 : OFF ; 1 : ON
0 : OFF ; 1 : ON
0 : OFF ; 1 : ON
20
20 - 80
0 : OFF ; 1 : ON
0 : OFF ; 1 : ON
0
0 - 100
0
0 : OFF ; 1 : ON
1
1 - 10
(%)
1
1 - 5
0:OFF;1:ON
0 : OFF ; 1 : ON
0
0-50
th
Parameter
Relay1 - Relay 12/14*
8/12/14*
Parameter
Relay1 - Relay 12/14*
8/12/14*
Length
Data
(Register)
Structure
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
1
Integer
Signed
1
Integer
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
Integer
1
1
Integer
Integer
1
Integer
1
1
Integer
1
Integer
Integer
1
Integer
1

Advertisement

loading