6. Installation
6.3 Grounding the cabinets
When installing multiple cabinets in a row, daisy-chain the grounding cables as shown in Figure 6-2, and
connect the last grounding cable to ground via a ground bar.
Cabinet 1
Figure 6-2 Connecting cabinets to ground (multiple cabinets in a row)
Because each cabinet is grounded at a single point, the cabinet must be insulated from the base.
Figure 6-3 shows an example of insulating the base.
Spring washer
Cabinet 2
Grounding cables (22 mm
Ground bar
At least class D grounding with the
ground resistance of 100Ω or less
Bolt
Washer
Insulating bush
Insulating
plate
Figure 6-3 Example of base insulation
6-2
Cabinet 3
2
Door
Cabinet frame
Base
Cabinet
grounding point
Insulating plate
Base
braided wire)