3.5 SERVOPACK Reference Offset Adjustment

When the SVA-01 Module connected SERVOPACK is used for speed control mode, the servomotor may rotate slowly
even if 0 V is specified as the analog reference. This happens if the SVA-01 Module has a slight offset in the reference
voltage. Adjustments can be done manually or automatically by using the panel operator or digital operator.

3.5.1 Automatic Adjustment of the Analog Reference Offset

The automatic adjustment of the analog (speed/torque) reference offset (Fn009) automatically measures the amount of
the offset and adjusts the reference voltage.
After completion of the automatic adjustment, the amount of offset is stored in the SERVOPACK. The amount of offset
can be checked in the speed reference offset manual servo tuning (Fn00A).
 When the SVA-01 Module is used to form a position loop, the automatic adjustment of analog reference offset
(Fn009) cannot be used. In this case, use the speed reference offset manual servo tuning (Fn00A).
 SERVOPACKs are provided with the zero-clamp speed control function to force the motor to stop while the zero
speed reference is given. Refer to the following manuals for details.
 AC Servo Drives
 AC Servodrive
Rotational Motor Analog Voltage and Pulse Train Reference (Manual No. SIEP S800000 45)
 AC Servodrive
Linear Motor Analog Voltage and Pulse Train Reference (Manual No. SIEP S800000 47)
Σ
-7-Series AC Servo Drive
(Manual No.: SIEP S800001 26)
 The speed reference offset must be automatically adjusted with servo OFF.
Adjust the speed reference offset automatically using the following procedures.
1.
Make sure that the servo is OFF. Set the motion setting parameter OL10 (Speed Reference Set-
ting) to 0 and then set the motion parameter OW08 (Motion Command) to 23 to send the VELO
(Speed Reference) command. Input 0-V reference voltage from the SVA-01 Module.
The servomotor will slightly turn.
2.
Press the MODE/SET Key on the panel operator to select the utility function mode.
"Fn000" will be displayed.
3.
Press the
erence offset).
Reference
voltage
Offset
Speed (torque)
reference
Σ

-III Series SGM
/SGDS User's Manual (Manual No. SIEP S800000 00)
Σ

-V Series SGM
/SGDV User's Manual Design and Maintenance
Σ
-I Series User's Manual Design and Maintenance
Σ
-7S SERVOPACK with Analog Voltage/Pulse Train References Product Manual
(UP) or
(DOWN) Key to select Fn009 (Automatic tuning of analog (speed, torque) ref-

3.5 SERVOPACK Reference Offset Adjustment

3.5.1 Automatic Adjustment of the Analog Reference Offset

Reference
voltage
Automatic
offset
adjustment
Speed (torque)
reference
3-13