SCALANCE W774/W734 RJ-45
For the power supply, there are two options with the SCALANCE W774/W734:
• Direct feed in via the four-pin socket (position ①)
For the direct feed-in power supply use copper cables with the following properties:
– Round cable cross-section with 6 to 8 mm diameter.
– Two-wire cable with 0.5 to 1.5 mm2 cross-section per wire.
– Permitted tensile load at least 100 N. - UL
– Listing of the cables according to the national installation regulations. In areas
• Power over Ethernet via the RJ-45 Ethernet interface P2 (position ②). The other
Ethernet interface P1 is not capable of PoE.
The four-pin connecting socket has the following pin assignment:
Pin
L1+
M1
M2
L2+
SCALANCE W774-1 /W734-1
Operating Instructions, 07/2020, C79000-G8976-C325-14
where NEC or CEC applies: Type PTLC or ITC
Assignment
24 VDC
Ground
Ground
24 VDC
Connection
5.2 Power supply