Phase Detection; Pressure Switch - LG MULTI V IV ARNU07GTU 2 Series Service Manual

Hide thumbs Also See for MULTI V IV ARNU07GTU 2 Series:
Table of Contents

Advertisement

3.4 Phase detection

n Power lines are connected correctly like follow case, product do not work and display error no.
Case 1) Missed connect 1 or more phase line.
Case 2) N phase line is incorrectly connected.
Case
Missed Phase
Reversed Phase
h The error occur 2 or more unit of the series at the same time, only a small unit number will be displayed.
Example) Master and Slave2 occur error no. 50, ʻ501ʼ display on the 7segment.
* Master: ***1, Slave1:***2, Slave2:***3, Slave3:***4

3.5 Pressure switch

- Main has pressure sensing switch in series between compressor and power relay.
- The state of pressure sensing switch is normally on. It has small electric current from 220V AC. Never touch
the connecting terminal with hand nor short two wires directly.
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Terminal block
R
S
X
X
N
N
T
X
N
- 27 -
Function
Error No.
N
50
5
X
25
50
5
N
No error
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi v iv arnu09gtu 2 seriesMulti v iv arnu12gtu 2 seriesMulti v iv arnu05gtr 2 seriesMulti v iv arnu07gtr 2 seriesMulti v iv arnu09gtr 2 seriesMulti v iv arnu12gtr 2 series ... Show all

Table of Contents