Liquid Lines; Refrigerant Line Charge - York E1FB180 Installation Instructions Manual

Split-system heat pumps outdoor units
Table of Contents

Advertisement

035-16192-001-A-1001
TABLE 5 - LIQUID LINES
Model Designation
System 1
180
System 2
System 1
240
System 2
1
Based on Refrigerant-22 at the nominal capacity of the condensing unit, a liquid temperature of 105°F and a suction temperature of 40°F.
2
These friction losses do not include any allowances for a strainer, filter-drier, solenoid valve, isolation valve or fittings.
3
The total pressure drop of the liquid line for both friction and vertical rise must not exceed 40 PSI. If the pressure drop exceeds 40 PSI, the liquid refrigerant could flash before it reaches the
TABLE 6 - REFRIGERANT LINE CHARGE
Refrigerant
2
Line
Liquid
Vapor
1
Charges are based on 40°F suction temperature and 105°F liquid temperature.
2
Type "L" copper tubing.
Use these line charges to adjust the system operating
charge when the refrigerant lines are more or less than the
25 feet listed in Table 2.
Turn the stem in (or clockwise) between 1/4 and 1/2 turn to
open the access port.
As soon as some internal pressure is relieved, close the ac-
cess port. DO NOT remove the entire holding charge.
NOTE: The copper disc on the liquid connection will prevent
any internal pressure from being relieved through the
main port of the liquid line stop valve.
If the unit has already lost its holding charge, it should be
leak tested and the necessary repairs should be made. If the
unit has maintained its holding charge, you can assume that
it has no leaks and proceed with the installation.
CAUTION: Dry nitrogen should always be supplied through a
connection while it is being brazed or unbrazed be-
cause the temperature required to make or break a
brazed joint is sufficiently high to cause oxidation
of the copper unless an inert atmosphere is pro-
vided. The flow of nitrogen should be continued
until the joint has cooled.
WARNING The dry nitrogen must always be supplied through
a pressure regulating valve.
Before installing the liquid line between the outdoor and in-
door units, remove the copper disc from the liquid connection
on the outdoor unit per the following procedure:
Make sure the refrigerant in the line has been recovered
and that the liquid service valve on the unit is front-seated
and closed. The valve stem should be turned to its maxi-
mum clockwise position.
Drill a small hole through the disc before unbrazing it to per-
mit a flow of dry nitrogen through the connection while it is
being unbrazed.
WARNING: This hole is also required to prevent the internal
pressure from building up as the disc is being un-
brazed and from blowing the disc off.
8
Nominal
Capacity
(Tons)
7-1/2
10
Line Size,
Refrigerant Charge
1
OD (In.)
(Lb/Ft)
5/8
0.113
1-1/8
0.013
1-3/8
3.
1.
2.
Refrigerant
Type L
1
Flow Rate
Copper Tubing
(Lbs./Min.)
(Inches O.D.)
22.5
5/8
30.0
5/8
This warning applies to any disc being removed
from a service valve, coil connection, etc.
Remove the cap from the 1/4" access port on the liquid line
stop valve.
Connect a supply of dry nitrogen to this access port.
Unbraze the copper disc from the liquid connection while
maintaining a minimum flow of dry nitrogen through the
connection.
After the disc has been removed,
Burnish the external surfaces of the liquid connection on
the outdoor unit and the end of the field-supplied piping be-
ing used for the liquid line.
NOTE: Clean surfaces are essential for a well brazed connec-
tion.
2. Carefully clean the internal surfaces of the above. Any par-
ticles left on these surfaces may lead to a future system
malfunction.
NOTE: Use only copper tubing that has been especially
cleaned and dehydrated for refrigerant use. If the tub-
ing has been open for an extended period of time, it
should be cleaned before being used.
The liquid line connections can now be brazed while maintain-
ing a minimum flow of dry nitrogen through the piping.
NOTE: A filter-drier is factory-mounted in the outdoor unit for
the heating cycle and in the indoor unit for the cooling
cycle.
Do NOT install another filter-drier in the field-supplied
liquid line because refrigerant will flow in both direc-
tions on a heat pump system.
Recover the holding charge of the indoor unit and then remove
the sealing caps or discs from both its liquid and vapor connec-
tions per the following procedure:
1. Make sure the refrigerant in the lines has been recovered,
then drill a small hole through both the liquid disc and the
vapor disc. If the holding charge has already been lost, the
coil should be leak-tested and the necessary repairs
should be made.
2. Move the dry nitrogen supply from the access port on the
liquid line service valve of the outdoor unit to the hole
through the vapor disc on the indoor unit.
3. Unbraze the coil's liquid line disc while maintaining a flow of
dry nitrogen across the connection and through the hole in
the liquid line disc.
3
Pressure Drop
Vertical
2
Friction
Rise
(PSI/100 Ft.)
(PSI/Ft.)
3.5
0.5
5.8
0.5
3.
4.
5.
1.
Unitary Products Group

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E1fb240E1fb180a25E1fb180a46E1fb240a25E1fb240a46

Table of Contents