General; System Sequence Of Operation; Cooling Operation; Refrigerant Flow Diagram - York E1FB180 Installation Instructions Manual

Split-system heat pumps outdoor units
Table of Contents

Advertisement

INDOOR
NON-ADJUSTABLE
COIL
THERMAL EXPANSION
VALVE FOR COOLING
(10°F SUPER HEAT)
BRAZED
CONNECTIONS
COOLING CYCLE FLOW
KEY
HEATING CYCLE FLOW
FIG. 6 - REFRIGERANT FLOW DIAGRAM

GENERAL

During the cooling cycle, when the reversing valve solenoids
becomes energized, operation will be the same as any conven-
tional air conditioning system.
During the heating cycle, when the reversing valve solenoids
becomes de-energized, compressor discharge gas will be di-
verted to the indoor coil and the outdoor coil will become the
evaporator.
Refer to Figure 6 for illustration showing the flow of refrigerant
through a heat pump system.
CAUTION: Reversing valves and check valves are precise
mechanical devices and will not tolerate any me-
chanical abuse such as hammering. If a refrigerant
system isn't properly cleaned after a compressor
burn-out, scale may build up at these devices and
prevent them from operating properly.
Unitary Products Group
NON-ADJUSTABLE
THERMAL EXPANSION
VALVE FOR HEATING
(5°F SUPER HEAT)
FILTER DRIERS
FIELD-INSTALLED
LIQUID LINE
FIELD-INSTALLED
VAPOR LINE
SERVICE VALVES WITH
COPPER STUB CONNECTIONS
OPERATION

SYSTEM SEQUENCE OF OPERATION

The following sequences of operation are based on using the
manual changeover thermostat. Refer to the respective unit
wiring diagram.

COOLING OPERATION

The following controls will be energized through terminal O
on the thermostat to put the system in the cooling mode.
Relays RY3, RY4, RY5, and RY6
If the fan switch on the thermostat is in the "ON" position, in-
door section blower motor contactor 10M will be energized
through terminal G to provide continuous blower operation.
If the switch is in the "AUTO" position, the blower will oper-
ate only when the thermostat calls for cooling operation.
3. When TC1 of the thermostat closes on demand for cooling,
a circuit is made from the Y terminal on DC1 and DC2
035-16192-001-A-1001
OUTDOOR
COIL
CHECK
VALVE
REVERSING
VALVE WITH
24-VOLT
SOLENOID
COMPRESSOR SUCTION LINE
ACCUMULATOR
1.
2.
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E1fb240E1fb180a25E1fb180a46E1fb240a25E1fb240a46

Table of Contents