York 036-048 Technical Manual page 13

Split-system heat pumps 10 seer – r-22
Table of Contents

Advertisement

HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
EVAPORATOR COIL MODEL NO
AIR TEMP.
AIR TEMP.
ENTERING
ENTERING
OUTDOOR
INDOOR
UNIT
60
47
40
30
17
10
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
Air Handler
Coil
MA16CN2,4
FC/MC48C3X
N1AHC1646
G2FD048(S,H)21
MA20DN2,4
MC48D3X
N1AHD2046
G2FD048(S,H)24
AHP/SHP48D3X
F2FP060
G1FA048S21
G1NA048S21D
G1UA048S21
FC/MC/PC/UC48C,D3X
G2FD048(S,H)21,24
Unitary Products Group
E2RA048S(25,46)
F2RP/F2FP048
1250
MBTUH
KW
COIL
60
53.4
4.86
70
54.2
4.76
80
54.1
5.57
60
47.0
4.54
70
46.9
4.56
80
46.3
5.24
60
37.7
3.54
70
37.3
3.98
80
36.6
5.79
60
37.7
4.01
70
36.7
4.16
80
35.3
4.60
60
32.2
3.67
70
30.8
3.98
80
29.4
4.30
60
29.2
3.46
70
27.5
3.81
80
25.8
4.02
MBH KW
1.00
1.00
1.00
1.02
1.00
1.02
1.00
1.02
1.01
1.02
1.01
1.02
1.00
1.02
1.00
1.04
1.00
1.03
1.00
1.03
1.00
1.03
ID CFM
1400
C.O.P.
MBTUH
KW
3.23
52.9
4.72
3.34
54.1
4.61
2.85
54.4
5.39
3.03
46.6
4.45
3.02
47.0
4.47
2.59
46.9
5.13
3.12
42.9
4.31
2.75
42.9
4.40
1.85
42.5
5.00
2.76
38.7
4.03
2.58
38.2
4.22
2.25
37.3
4.70
2.57
32.7
3.68
2.27
31.4
3.97
2.00
30.1
4.29
2.48
29.6
3.46
2.12
27.9
3.80
1.88
26.3
4.02
COP
0.97
0.98
0.98
0.98
0.99
0.99
0.98
0.96
0.97
0.97
0.97
279104-YTG-B-0307
1550
C.O.P.
MBTUH
KW
3.28
52.2
4.25
3.44
53.7
4.14
2.96
54.4
4.83
3.07
46.5
4.05
3.08
47.2
4.06
2.68
47.3
4.65
2.92
43.4
3.93
2.86
42.6
4.13
2.50
40.0
5.47
2.82
37.9
3.70
2.65
38.4
3.93
2.33
38.7
4.44
2.61
33.0
3.40
2.32
31.8
3.66
2.06
30.6
3.94
2.51
30.1
3.19
2.15
28.4
3.51
1.92
26.7
3.71
C.O.P.
3.61
3.80
3.30
3.36
3.41
2.98
3.24
3.02
2.14
3.00
2.86
2.55
2.85
2.55
2.28
2.77
2.37
2.12
13