Appendix 9 : Using the e7w CBL32 Registry Viewer/Editor

Use the rEG parameter to view or modify CBL32 Registry Group 9 Thermo/HVAC and Registry Group 7:X:Y input/output in
the HVAC Partner device (i.e. X47) to the e7w.
1. Enter SERVICE MODE
2. Use the UP/DOWN arrow buttons to select rEG
3. Press MODE. This action displays Gr (Group) value.
4. Use the UP/DOWN arrow buttons to change the Gr value to the required CBL32 Group.
For example, Group 9 for Thermostat 9: X registries, or Group 7 for 7: X Input/Output registry's.
5. Press the MODE button. This action displays KEY value (This is the Registry Key value).
6. Use the UP/DOWN arrow buttons to change the KEY value to the required CBL32 Key.
For example, 9:1 - Group 9: Key 1 Occupancy or 7:3 - Group 7: Key 3 Light Output
41 of 47
Honeywell Restricted
13 April 2020
Version 9.0