TABLE 6: DH 240 COOLING CAPACITIES (20 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
POWER
1
CAP.
INPUT
WB
MBH
CFM
°F
77
217.3
72
207.2
6000
67
197.0
62
194.2
57
192.4
77
226.2
72
215.6
7000
67
205.0
62
202.1
57
200.2
77
235.0
72
224.0
8000
67
213.0
62
210.0
57
208.0
72
236.1
67
224.5
9000
62
221.3
57
219.2
72
248.2
67
236.0
10000
62
232.7
57
230.5
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-
mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating
Johnson Controls Unitary Products
115°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
2
KW
90
85
80
24.8
139.8 111.3
82.8
24.3
175.4 146.9 118.4
89.9
23.9
197.0 182.5 154.0 125.5
23.5
194.2 194.2 173.0 144.5 116.0
23.2
192.4 192.4 172.2 143.7 115.2
23.8
184.2 131.0
91.4
23.4
198.1 164.4 130.7
97.0
23.0
205.0 197.8 170.0 136.3 102.6
22.5
202.1 202.1 191.0 157.3 123.6
22.3
200.2 200.2 190.1 156.4 122.7
22.8
228.5 150.8 100.0
22.4
220.8 181.9 143.0 104.1
22.0
213.0 213.0 186.0 147.1 108.2
21.6
210.0 210.0 209.0 170.1 131.2
21.4
208.0 208.0 208.0 169.1 130.2
20.0
234.5 202.5 158.2 113.9
19.6
224.5 224.5 205.8 161.5 117.2
19.2
221.3 221.3 220.8 176.6 132.3
19.1
219.2 219.2 219.2 175.0 130.7
17.5
248.2 223.0 173.4 123.7
17.2
236.0 236.0 225.5 175.8 126.1
16.9
232.7 232.7 232.7 183.0 133.3
16.7
230.5 230.5 230.5 180.8 131.1
75
70
65
-
-
-
-
-
97.0
-
87.5
86.7
-
-
-
-
-
-
89.9
89.0
-
-
-
-
-
-
92.4
91.4
-
-
-
88.0
86.4
-
-
-
83.6
81.4
262260-YTG-E-1008
15