York CHAMPION D2EB Installation Instructions Manual page 7

Champion series single package air conditioners electric/electric, air-cooled
Table of Contents

Advertisement

174065-YIM-A-0206
Checking Supply Air CFM
To check the supply air CFM after the initial balancing has been
completed:
1.Remove the two ¼ inch dot plugs in the duct panel.
2.Insert at least 8 inches of ¼ inch tubing into each of these
holes for sufficient penetration into the airflow on both sides of
the indoor coil.
3.Using an inclined manometer, determine the pressure drop
across the dry evaporator coil. Since the moisture on an evapo-
rator coil may vary greatly, measuring the pressure drop across
a wet coil under field conditions would be inaccurate. To ensure
DEB018
0.4
0.35
0.3
0.25
0.2
0.15
0.1
0.05
0
400
600
-0.05
Unitary Products Group
DEB Coil Delta P vs Airflow
DEB024
800
1000
1200
Airflow (CFM)
a dry coil, the compressors should be deactivated while the test
is being run.
4.Knowing the pressure drop across a dry coil, the actual CFM
through the unit can be determined from the curve in Coil Delta
P vs. Supply Air CFM figure.
WARNING! Failure to properly adjust the total system air quan-
tity can result in extensive system damage.
After readings have been obtained, remove the tubes and rein-
stall the two ¼ inch plugs removed in Step 1.
NOTE: De-energize the compressors before taking any test
measurements to ensure a dry indoor coil.
1400
1600
1800
DEB048
DEB018
DEB048
DEB024
DEB030, 36, & 42
DEB060
DEB060
DEB030-42
2000
2200
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents