ZJ180-300 - High Static Drive Without Powered Convenience Outlet (Continued)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA MCC
208-3-60 23.0
160
230-3-60 23.0
160
300
(25)
460-3-60 12.2
87
575-3-60 8.7
62
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
FLA
FLA
FLA
31.5
3.7
38.6
0.0
31.5
3.7
38.6
0.0
17.1
1.9
19.3
0.0
13.5
1.5
15.4
0.0
Electric Heat Option
Model
kW
Stages
Amps
None
-
-
-
E18
13.5
1
37.5
E36
27.0
2
74.9
E54
40.6
2
112.7
E72
54.1
2
150.2
None
-
-
-
E18
18.0
1
43.3
E36
36.0
2
86.6
E54
54.0
2
129.9
E72
72.0
2
173.2
None
-
-
-
E18
18.0
1
21.7
E36
36.0
2
43.3
E54
54.0
2
65.0
E72
72.0
2
86.6
None
-
-
-
E18
18.0
1
17.3
E36
36.0
2
34.6
E54
54.0
2
52.0
E72
72.0
2
69.3
251934-YTG-J-0910
2
Max Fuse
/
1
3
MCA
Breaker
(Amps)
Size
(Amps)
155.1
175
155.1
175
155.1
175
189.1
200
198.4
225
155.1
175
155.1
175
156.5
175
178.2
200
221.5
250
80.5
90
80.5
90
80.5
90
89.1
100
110.7
125
60.1
70
60.1
70
62.6
70
71.2
80
88.5
100
75