York 251934-YTG-J-0910 Technical Manual page 67

R-410a zj/zr/zf series 15 - 25 ton 60 hertz
Table of Contents

Advertisement

Altitude/Temperature Correction Factors
Air
Temp.
0
1000
40
1.060
1.022
50
1.039
1.002
60
1.019
0.982
70
1.000
0.964
80
0.982
0.947
90
0.964
0.929
100
0.946
0.912
1.100
1.050
1.000
0.950
0.900
0.850
0.800
0.750
0.700
0.650
0.600
Gas Heat Minimum Supply Air
Size
(Tons)
180
(15)
210
(17.5)
240
(20)
300
(25)
For units with VFD and gas heat, the speed of the indoor
blower motor continues to be controlled by duct static
pressure via the VAV control board.
If there are VAV boxes present in the duct system,
the boxes must be driven to the full-open position
using a customer-supplied power source to assure
adequate airflow across electric heating elements
or gas heat exchanger tubes.
Johnson Controls Unitary Products
2000
3000
0.986
0.950
0.966
0.931
0.948
0.913
0.930
0.896
0.913
0.880
0.897
0.864
0.880
0.848
40
50
Heat Size
Min
24
4500
32
4500
24
6000
32
6000
24
6000
32
6000
24
7500
32
7500
Altitude (Ft.)
4000
5000
6000
0.916
0.882
0.849
0.898
0.864
0.832
0.880
0.848
0.816
0.864
0.832
0.801
0.848
0.817
0.787
0.833
0.802
0.772
0.817
0.787
0.758
60
70
80
Air Temperature (ºF)
Supply Air (CFM)
Cooling
Max
Min
7000
4500
7000
4500
8750
6000
8750
6000
9400
6000
9400
6000
12500
7500
12500
7500
7000
8000
0.818
0.788
0.802
0.772
0.787
0.757
0.772
0.743
0.758
0.730
0.744
0.716
0.730
0.703
Sea Level
1000 ft
2000 ft
3000 ft
4000 ft
5000 ft
6000 ft
7000 ft
8000 ft
9000 ft
10000 ft
90
100
Heating
Max
7000
7000
8750
8750
9400
9400
12500
12500
251934-YTG-J-0910
9000
10000
0.758
0.729
0.743
0.715
0.729
0.701
0.715
0.688
0.702
0.676
0.689
0.663
0.676
0.651
67