Flow Regulation; Flushing - Carrier Aquazone 50HQP Series Installation, Start-Up And Service Instructions Manual

Large capacity water source heat pumps
Hide thumbs Also See for Aquazone 50HQP Series:
Table of Contents

Advertisement

Table 6 — 50HQP,VQP Typical Unit Operating Pressures and Temperatures (cont)
50HQP,
ENTERING
50VQP
WATER
UNIT
TEMP
(GPM/ton)
SIZE
(F)
30
40
50
60
300
70
80
90
100
30
40
50
60
360
70
80
90
100

Flow Regulation

Flow regulation can be accomplished by two methods. Most water
control valves have a flow adjustment built into the valve. By
measuring the pressure drop through the unit heat exchanger, the
flow rate can be determined. Adjust the water control valve until
the flow of 1.5 to 2 gpm is achieved. Since the pressure constantly
varies, two pressure gages may be needed in some applications.
An alternative method is to install a flow control device. These
devices are typically an orifice of plastic material designed to al-
low a specified flow rate that are mounted on the outlet of the wa-
ter control valve. Occasionally these valves produce a velocity
noise that can be reduced by applying some back pressure. To ac-
complish this, slightly close the leaving isolation valve of the well
water setup.
WARNING
To avoid possible injury or death due to electrical shock, open
the power supply disconnect switch and secure it in an open
position before flushing system.

Flushing

Once the piping is complete, final purging and loop charging is
needed. A flush cart pump of at least 1.5 hp is needed to achieve
adequate flow velocity in the loop to purge air and dirt particles
from the loop. Flush the loop in both directions with a high vol-
ume of water at a high velocity. Follow the steps below to properly
flush the loop:
1. Verify power is off.
2. Fill loop with water from hose through flush cart before
using flush cart pump to ensure an even fill. Do not allow
the water level in the flush cart tank to drop below the
pump inlet line to prevent air from filling the line.
WATER
Suction
Discharge
FLOW
Pressure
Pressure
(psig)
(psig)
45.0
75.0
45.0
117-143
210-256
75.0
114-139
196-239
45.0
120-147
243-297
75.0
117-143
227-277
45.0
123-150
276-337
75.0
119-146
258-315
45.0
126-154
309-378
75.0
122-149
289-353
45.0
129-157
343-419
75.0
125-153
320-391
45.0
132-161
376-459
75.0
128-156
351-429
45.0
134-164
409-500
75.0
131-160
382-467
50.0
90.0
50.0
121-148
184-225
90.0
117-143
167-204
50.0
123-151
222-271
90.0
119-145
202-247
50.0
125-153
260-318
90.0
120-147
237-289
50.0
127-155
298-365
90.0
122-149
271-331
50.0
129-158
336-411
90.0
124-152
306-374
50.0
131-160
374-458
90.0
126-154
340-416
50.0
133-162
413-504
90.0
128-156
375-458
COOLING
Water
Air Temp
Temp
Drop
Rise
(F) DB
(F)
15-19
21-26
11-14
22-27
15-18
20-25
11-14
21-26
14-17
20-24
11-13
21-25
14-17
19-24
10-13
20-25
13-16
19-23
10-12
19-24
13-16
18-22
10-12
19-23
12-15
17-21
9-11
18-22
17-21
18-22
10-13
19-23
17-20
17-21
10-12
18-23
16-19
17-21
10-12
18-22
15-19
17-20
9-11
18-21
14-18
16-20
9-11
17-21
14-17
16-19
8-10
17-20
13-16
15-19
8-10
16-20
3. Maintain a fluid level in the tank above the return tee to
avoid air entering back into the fluid.
4. Shutting off the return valve that connects into the flush
cart reservoir will allow 50 psig surges to help purge air
pockets. This maintains the pump at 50 psig.
5. To purge, keep the pump at 50 psig until maximum pump-
ing pressure is reached.
6. Open the return valve to send a pressure surge through the
loop to purge any air pockets in the piping system.
7. A noticeable drop in fluid level will be seen in the flush
cart tank. This is the only indication of air in the loop.
NOTE: If air is purged from the system while using a 10 in. PVC
flush tank, only a 1 to 2 in. level drop will be noticed since liquids
are incompressible. If the level drops more than this, flushing
should continue since air is still being compressed in the loop. If
level is less than 1 to 2 in., reverse the flow.
1. Repeat this procedure until all air is purged.
2. Restore power.
Antifreeze may be added before, during or after the flushing pro-
cess. However, depending on when it is added in the process, it
can be wasted. Refer to the Antifreeze section for more detail.
Loop static pressure will fluctuate with the seasons. Pressures will
be higher in the winter months than during the warmer months.
This fluctuation is normal and should be considered when
charging the system initially. Run the unit in either heating or cool-
ing for several minutes to condition the loop to a homogenous
temperature.
When complete, perform a final flush and pressurize the loop to a
static pressure of 40 to 50 psig for winter months or 15 to 20 psig
for summer months.
37
HEATING
Water
Suction
Discharge
Temp
Pressure
Pressure
Drop
(psig)
(psig)
(F)
68- 84
256-313
5- 7
73- 89
261-319
4- 5
81- 99
277-339
7- 8
86-105
283-346
5- 6
93-114
299-365
8- 9
99-121
305-373
6- 7
106-129
321-392
9-11
113-138
327-400
7- 8
118-145
342-418
10-12
126-154
349-427
8- 9
131-160
364-444
11-14
139-170
371-454
8-10
143-175
385-471
12-15
152-186
393-480
9-11
65- 80
282-344
6- 7
73- 89
294-359
3- 4
80- 98
299-365
7- 9
89-108
311-380
4- 5
95-116
315-385
9-11
105-128
329-402
5- 7
109-133
332-406
11-13
121-148
346-423
6- 8
124-151
349-427
12-15
138-168
364-444
7- 9
138-169
366-447
14-17
154-188
381-466
8-10
153-187
383-468
16-19
170-208
399-487
9-12
Air Temp
Rise
(F) DB
19-23
20-25
22-26
23-28
24-29
25-31
26-32
28-34
29-35
30-37
31-38
33-40
33-41
35-43
14-17
15-18
16-20
17-21
19-23
20-24
21-26
22-27
23-28
25-30
26-31
27-33
28-34
29-36

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents