Fig. 17 — VFD Input and Output Power Connections, 50HQP Units
50HQP UNIT
VOLTAGE
SIZE
(V-Ph-Hz)
208/230-1-60
072
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
096
460-3-60
575-3-60
208/230-1-60
208/230-3-60
120
460-3-60
575-3-60
208/230-3-60
150
460-3-60
575-3-60
208/230-3-60
180
460-3-60
575-3-60
208/230-3-60
242
460-3-60
575-3-60
Table 2 — 50HQP072-242 Electrical Data
COMPRESSOR (x2)
RLA
LRA
16.7
79.0
10.4
73.0
5.8
38.0
19.6
130.0
13.7
83.0
6.2
41.0
4.8
33.0
26.3
134.0
15.6
110.0
7.8
52.0
5.8
38.9
19.2
136.0
8.7
66.1
6.9
55.3
22.4
149.0
10.6
75.0
7.7
54.0
30.1
225.0
16.7
114.0
12.2
80.0
19
BLOWER MOTOR
QTY
FLA
HP
1
7.0
1
1
3.6
1
1
1.8
1
1
9.8
2
1
6.2
2
1
3.1
2
1
2.6
2
1
9.8
2
1
8.0
3
1
3.9
3
1
3.7
3
1
9.2
3
1
4.3
3
1
3.7
3
2
6.2
2
2
3.1
2
2
2.6
2
2
3.9
2
2
3.1
2
2
2.6
2
MIN CIRCUIT
MAX FUSE/
AMPS
HACR
44.6
60
27.0
35
14.9
20
53.9
70
37.0
50
17.1
20
13.4
15
69.0
90
43.1
50
21.5
25
16.8
20
52.4
70
23.9
30
19.2
25
62.8
80
30.1
40
22.5
30
75.5
100
43.8
60
32.7
40