Specifications - Omron K8DT-PM Manual

Three-phase voltage and phase-sequence phase-loss relay
Table of Contents

Advertisement

K8DT-PM
Ratings and Specifications
Ratings
K8DT-PM1@N: Three-phase, three-wire Mode:
200, 220, 230, or 240 VAC
Rated input voltage
K8DT-PM2@N: Three-phase, three-wire Mode:
380, 400, 415, or 480 VAC
K8DT-PM1: Approx. 1.7 VA
Input load
K8DT-PM2: Approx. 2.7 VA
Rated insulation
528 VAC
voltage
Overvoltage
30% to 30% of rated input voltage
Operating value setting
Undervoltage
30% to 30% of rated input voltage
range
Note: The rated input voltage can be switched
Operating value
Operates at 100% of set value.
Reset value
5% of operating value (fixed)
Reset method
Automatic reset
Overvoltage/
0.1 to 30 s
Operating
Undervoltage
time
Phase
setting
0.1 s0.05 s
sequence
range
Phase loss
0.1 s max.
Power ON lock time
1 s5 s (switched by using the DIP switch)
Power (PWR): Green, Output (OUT): Yellow,
Indicators
OVER: Red, UNDR: Red
Relay: SPDT contact output
Output form
Transistor: Open collector
Rated load
5 A at 250 VAC (Resistive load)
5 A at 30 VDC (Resistive load)
1 A at 250 VAC (Inductive load)
0.2 A at 48 VDC (Inductive load)
Output relay ratings
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life: 5 A at 250 VAC or 30 VDC:
Contact form: SPST-NO (Open collector)
Transistor output
Rated voltage: 24 VDC (maximum voltage: 26.4 VDC)
ratings
Maximum current: 50 mA DC
Ambient operating
20 to 60°C (with no condensation or icing)
temperature
25 to 65°C (with no condensation or icing)
Storage temperature
Ambient operating
25% to 85% RH (with no condensation)
humidity
Storage humidity
25% to 85% RH (with no condensation)
Altitude
2,000 m max.
Applicable wires
Stranded wires, solid wires, or ferrules
Applicable wire size
0.25 to 1.5 mm
Wire insertion force
8 N max. for AWG20 wire
Screwdriver
15 N max.
insertion force
Wire stripping length
8 mm
Ferrule length
8 mm
Current capacity
10 A (per pole)
Number of insertions
50 times
Case color
N1.5
Case material
PC, UL 94 V-0
Weight
Approx. 100 g
Mounting
Mounts to DIN Track, or screw mounting
17.5  90  90 mm (WDH)
Dimensions
2
by using the DIP switches.
50,000 operations
3 A at 250 VAC or 30 VDC:
100,000 operations
2
(AWG24 to AWG16)

Specifications

Input frequency
50/60 Hz
Overload capacity
Continuous 528 V
0.5% full scale (at 25C and 65% humidity, rated
Operating
value
power supply voltage)
Repeat
accuracy
50 ms (at 25C and 65% humidity, rated power
Operating
time
supply voltage)
EN 60947-5-1
Conforming
Installation environment (pollution level 2,
standards
Overvoltage category III)
Applicable
EMC
EN 60947-5-1
standards
UL 60947-5-1 (Listing), Korean Radio Waves Act
Safety
(Act 10564), CCC (GB14048.5), LR (Category
standards
ENV1.2) *
20 M min.
Insulation resistance
Between external terminals and case
Between input terminals and output terminals
2,000 VAC for one minute
Dielectric strength
Between external terminals and case
Between input terminals and output terminals
1,500 V power supply terminal common/normal
mode
Noise immunity
Square-wave noise of 1 s/100 ns pulse width
with 1-ns rise time
Impulse withstand
6 kV (between live terminals and exposed, non-
voltage
charged metal parts)
Frequency: 10 to 55 Hz, 0.35-mm single
Vibration resistance
amplitude, acceleration 50 m/s
10 sweeps of 5 min each in X,Y, and Z directions
100 m/s
Shock resistance
axes
Degree of protection
Terminals: IP20
* Certification is pending for LR.
2
2
, 3 times each in 6 directions along 3

Advertisement

Table of Contents
loading

This manual is also suitable for:

K8dt-pm1cnK8dt-pm1tnK8dt-pm2cnK8dt-pm2tnK8dt-pm series

Table of Contents