Performance Features; System Description - Bosch FCP‑O 500 Operation Manual

Conventional automatic detectors
Hide thumbs Also See for FCP‑O 500:
Table of Contents

Advertisement

6
en | Product Description
- FCA-500-E-EU
Mounting Boxes:
- FAA-500-BB
- FAA-500-CB
- FAA-500-SB-H
Service Accessories:
- FAA-500-RTL
- FAA-500-TTL
1.1

Performance Features

1.2

System Description

All detectors in the 500 Series are equipped with two optical sensors and a pollution sensor.
The FCP‑OC 500 Multisensor Detector contains a gas sensor as an additional detection
channel.
All sensor signals are analyzed continually by the internal signal evaluation processor and are
linked with each other by specially developed algorithms.
By linking the optical sensors and the gas sensor, the OC detector can also be used in places
where the work carried out gives rise to small amounts of smoke, steam or dust. The alarm
will only be triggered automatically if the signal combination corresponds with the detector's
programmed characteristic diagram. Consequently, an extremely high tolerance to unwanted
alarms is achieved.
2019.11 | 5.0 | F.01U.003.962
Conventional Detector Base with EOL resistor
Ceiling Mount Back Box
Built-in Housing for concrete ceilings
Surface Mount Back Box with damp room seal
Detector Exchanger for 500 and 520 Series Detectors
Test Adapter with Magnet for 500 and 520 Series Detectors
Fulfills the highest aesthetic demands through the flush-mounting design and the
possibility of color toning
Smooth, easily-cleaned detector surface
Quick and easy insertion and exchange of the detector thanks to innovative detector
locking mechanism (click and lock principle)
Easily-visible two-color LED for display of alarm, trouble and test mode
Self-monitoring of the sensors: contamination level can be read in test mode
Active adjustment of the threshold (drift compensation) if the optical sensor becomes
contaminated
Active adjustment of the threshold (drift compensation) of the chemical sensor
Increased detection and false alarm immunity thanks to evaluation of the time behavior of
fire and disturbance variables
Activation of a remote indicator is possible (not for relay bases)
Easily accessible connection terminals
Service accessories for simple and comfortable detector test and exchange
When using the FAA‑500‑TTL test adapter, an integrated reed switch automatically
switches the detector into the test mode (display via detector LED, flashes green once
per second).
Can be connected to the LSN fire panels FPA‑1200, FPA‑5000 (both with CZM module or
4CON module on LSN loop), UEZ 2000 LSN, UGM 2020 and to other fire panels or their
receiver modules with identical connection conditions.
EN 54‑7 certified.
Operation Guide
Conventional Automatic Detectors
Bosch Sicherheitssysteme GmbH

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcp‑oc 500Fcp‑o 500‑pFcp‑oc 500‑p

Table of Contents