Maytag Amana APC15 H Series Installation Instructions Manual

Self-contained package air conditioners and heat pump units with r-410a

Advertisement

I
I
NSTALLATION
NSTRUCTIONS
APC15 / APH 16 [15/16 SEER "H" SERIES]
S
-C
P
ELF
ONTAINED
ACKAGE
W
R-410A
ITH
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this
Installation Manual. Observe all safety warnings. During in-
stallation or repair, caution is to be observed.
It is your responsibility to install the product safely and to
educate the customer on its safe use.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation
of self contained package air conditioner and heating units. See
the Specification Sheets applicable to your model for informa-
tion regarding accessories.
*NOTE: Please contact your distributor or our website for the
applicable Specifications Sheets referred to in this manual.
"IMPORTANT - This product has been designed and manufactured to meet ENERGY STAR®
criteria for energy efficiency when matched with appropriate coil components. However,
proper refrigerant charge and proper air flow are critical to achieve rated capacity and
efficiency. Installation of this product should follow the manufacturer's refrigerant charging
and air flow instructions. Failure to confirm proper charge and air flow may reduce energy
efficiency and shorten equipment life."
IOA-3011D
02/2018
is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.
A
C
IR
ONDITIONERS AND
All information contained herein is subject to change without notice.
Goodman Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.amana-hac.com
© 2015-2018 Goodman Company, L.P.
H
P
U
EAT
UMP
NITS
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL
(
, "
REPAIR
HEREINAFTER
SERVICE
SHOULD SERVICE THE EQUIPMENT
FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR
. I
SERVICE PROCEDURES
F YOU SERVICE THIS UNIT
FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT
JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT
,
SPECIFIED IN THIS MANUAL
ONLY LICENSED PERSONNEL SHOULD SERVICE THE
. I
EQUIPMENT
MPROPER INSTALLATION
THE EQUIPMENT SPECIFIED IN THIS MANUAL
SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER
TRAINING MAY RESULT IN PRODUCT DAMAGE
.
INJURY OR DEATH
,
,
ADJUST
SERVICE OR
")
THE EQUIPMENT SPECIFIED IN THIS MANUAL
. T
HE MANUFACTURER WILL NOT BE RESPONSIBLE
,
YOU ASSUME RESPONSIBILITY
. I
N ADDITION
,
,
ADJUSTMENT
SERVICING OR REPAIR OF
,
OR ATTEMPTING TO INSTALL
,
,
PROPERTY DAMAGE
PERSONAL
,
IN
,
,
ADJUST

Advertisement

Table of Contents
loading

Summary of Contents for Maytag Amana APC15 H Series

  • Page 1 5151 San Felipe, Suite 500, Houston, TX 77056 02/2018 www.amana-hac.com © 2015-2018 Goodman Company, L.P. is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.
  • Page 2: Table Of Contents

    TO THE INSTALLER ..............2 TROUBLESHOOTING CHART ..........16 SHIPPING INSPECTION ............2 START-UP CHECKLIST ............18 Checking Product Received ..........2 Message to the Homeowner ..........3 NSTALLER REPLACEMENT PARTS ............3 Carefully read all instructions for the installation prior to installing Ordering Parts ..............
  • Page 3: Important Safety Instructions

    IMPORTANT SAFETY INSTRUCTIONS Recognize Safety Symbols, Words, and Labels WARNING The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner’s responsibility to read and comply with all safety information and instructions accompanying these symbols.
  • Page 4: National Codes

    CONTACT THE LOCAL OFFICE OF THE EPA. National Codes This product is designed and manufactured to permit installation in accordance with National Codes. It is the installer’s responsibility to install the product in accordance with National Codes and/or prevailing local codes and regulations. MAJOR COMPONENTS General The unit includes a hermetically sealed refrigerating system (consisting of a compressor, condenser coil, evaporator coil with flowrator),...
  • Page 5: Rooftop Installation

    Outside Slab Installation WARNING The unit must be mounted on a solid, level foundation. See Figure 1. Select a location that will minimize the length of the supply and return ducts. Select a location where external water drainage cannot collect around the unit.
  • Page 6 supply system. Ductwork should be properly supported from the unit. CAUTION NOTE: Proper sealing of all duct work and air handling compartments is extremely important to overall unit efficiency. Filters Filters are not provided with unit, and must be supplied and installed in the return duct system by the installer.
  • Page 7: Operation

    High Voltage Wiring BRANCH CIRCUIT AMPACITY 15 20 25 30 35 40 45 50 See Figure 6 SUPPLY WIRE LENGTH - FEET Single Phase- Two leads should be connected to terminals L1 & L2 in the electrical control section, using wire sizes specified in wiring table.
  • Page 8: Final System Checks

    12. If the out door ambient is above 80°F, the unit may HEAT PUMP REFRIGERANT CIRCUIT - Figure 7 trip on its high pressure cut out when on heating. The compressor should stop. The heating cycle must be thoroughly checked, so postpone the test to another day when conditions are more suitable but-DO NOT FAIL TO TEST.
  • Page 9: Defrost Control

    Defrost Control - The Defrost control provides time/temperature initiation and termination of the defrost cycle. When a Defrost cycle is initiated, the defrost control shifts the reversing valve to “cooling” mode, stops the outdoor fan and brings on supplemental heat. Normally, a Defrost cycle will take only 2-3 minutes unless system is low on charge or outdoor conditions are severe. (Windy and cold.) The defrost control also provides for a 3 minute off cycle compressor delay.
  • Page 10: Suggested Field Testing/Troubleshooting

    SUGGESTED FIELD TESTING/TROUBLE SHOOTING Run unit in the heating mode (room thermostat calling for heat). Check unit for proper charge. Note: Bands of frost on the condenser coil indicate low refrigerant charge. Shut off power to unit. Disconnect outdoor fan by removing the outdoor fan motor wire from “DF2” on defrost control. Restart unit and allow frost to accumulate.
  • Page 11: Application (Aph1624-36)

    APC15 / APH16 CFM Delivery and Adjustments See pages 14 and 15 for CFM Output, Adjustments and DIP switch settings. Thermostat “Fan Only” Mode During Fan Only Operations, the CFM output is 50% of the high stage cooling setting. Humidity Control When using a Humidistat (normally closed), cut jumper PJ6 on the control board.
  • Page 12 APC15H NOTE: Do NOT adjust charge based on suction pressure unless there is a gross undercharge. Design superheat @ 95 °F Disconnect manifold set. Installation is complete. outdoor ambient temperature Two Speed Application (APC1560/APH1642-60) Superheat Subcooling Model # Run the unit on low stage cooling for 10 minutes until refrigerant pressures stabilize. Follow ±...
  • Page 13: Electric Heat Installation & Adjustment

    ELECTRIC HEAT INSTALLATION & ADJUSTMENT WARNING This series of electric cooling and heat pump package equipment is HIGH VOLTAGE! designed to accept a field installed electric heat kit. The unit is equipped to easily install the HKR/HKP Series Electric Heat Kit. Full Installation Instructions are included in this kit.
  • Page 14: Adjusting Speed Tap For Indoor Blower Motor

    ADJUSTING SPEED TAP FOR INDOOR BLOWER MOTOR Evaporator Blower Specifications with ECM Motors APH1624H41 / APC1524H41 APH1630H41 / APC1530H41 Cooling/HP Adjust Electric Adjust Cooling/HP Adjust Electric Adjust CFM* CFM* CFM* CFM* Speed Heat Speed Heat Minus Minus Minus Minus Normal Normal Normal 1,073...
  • Page 15 SPEED SWITCH SWITCH COOLING/ HP SPEED SWITCH SWITCH ELECTRIC HEAT MODEL MODEL (CFM) (CFM) APC1524 APC1524 APH1624 APH1624 APC1530 APC1530 APH1630 1032 APH1630 1032 1,073 1,073 APC1536 1065 APC1536 1065 APH1636 1178 APH1636 1178 1270 1270 1219 1294 1219 APC1542 APH1642 1294 1323...
  • Page 16: Troubleshooting Chart

    TROUBLESHOOTING CHART HIGH VOLTAGE! ISCONNECT POWER BEFORE SERVICING OR INSTALLING THIS UNIT ULTIPLE POWER WARNING SOURCES MAY BE PRESENT AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH POSSIBLE CAUSE REMEDY SYMPTOM High head - low suction a.
  • Page 17 PACKAGE UNITS - HEAT PUMP AND AC UNITS HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS We strongly recommend a bi-annual maintenance checkup be performed by a qualified service agency before the heating and cooling seasons begin. coil with water. This cleaning practice remains as the recom- mended cleaning method for both copper tube and aluminum tube residential cooling coils.
  • Page 18: Start-Up Checklist

    Check filters and replace if necessary. Verify the installation of the thermostat. 9 /2 0 1 4 is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.
  • Page 19 Start-up Checklist Start-Up (Insert the values as each item is completed.) ELECTRICAL Supply Voltage L1 - L2 L2 - L3 L3 - L1 Circuit 1 Compressor Amps Circuit 2 Compressor Amps Blower Amps Condenser Fan Amps Fan 1 Fan 2 Fan 3 BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure...
  • Page 20 5151 San Felipe, Suite 500, Houston, TX 77056 www.amana-hac.com © 2015-2018• Goodman Company, L.P. is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX, USA. All rights reserved.

Table of Contents