Carrier WeatherMaker Puron 48FC 04 Series Installation Instructions Manual page 18

Single package rooftop gas heating/electric cooling unit with r-410a refrigerant
Hide thumbs Also See for WeatherMaker Puron 48FC 04 Series:
Table of Contents

Advertisement

GFCI (ground-fault circuit interrupter) duplex receptacle rated
at 15A behind a hinged waterproof access cover, located on the
end panel of the unit. See Fig. 29.
Figure 30 shows the Convenience Outlet Utilization label,
which is located below the convenience outlet.
CONVENIENCE
OUTLET GFCI
PWD-CO FUSE
SWITCH
PWD-CO
TRANSFORMER
Fig. 29 — Convenience Outlet Location
Fig. 30 — Convenience Outlet Utilization
Notice Label
NOTE: Unit powered convenience outlets are not available as fac-
tory installed options for single phase (-3 voltage code models).
Installing Weatherproof Cover
A weatherproof while-in-use cover for the factory-installed
convenience outlets is now required by UL standards. This
cover cannot be factory-mounted due its depth; it must be in-
stalled at unit installation. For shipment, the convenience outlet
is covered with a blank cover plate.
On units with electro-mechanical controls the weatherproof
cover kit is shipped in the unit's control box. The kit includes
the hinged cover, a backing plate, and gasket. On units with a
factory installed direct digital controller (SystemVu™ or RTU
Open) the weatherproof cover kit is secured to the basepan un-
derneath the control box (see Fig. 31).
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal inju-
ry or death.
Using unit-mounted convenience outlets: Units with unit-
mounted convenience outlet circuits will often require that
two disconnects be opened to de-energize all power to the
unit. Treat all units as electrically energized until the conve-
nience outlet power is also checked and de-energization is
confirmed. Observe National Electrical Code Article 210,
Branch Circuits, for use of convenience outlets.
WEATHERPROOF
COVER
Fig. 31 — Weatherproof Cover — Shipping Location
on Units with Factory Installed DDC
1.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
2.
Loosen the two screws at the GFCI duplex outlet, until
approximately
1/
2
exposed. Press the gasket over the screw heads.
3.
Slip the backing plate over the screw heads at the keyhole
slots and align with the gasket; tighten the two screws
until snug (do not over-tighten).
4.
Mount the weatherproof cover to the backing plate as
shown in Fig. 32.
5.
Remove two slot fillers in the bottom of the cover to per-
mit service tool cords to exit the cover.
6.
Check for full closing and latching.
COVER - WHILE-IN-USE
WEATHERPROOF
Fig. 32 — Weatherproof Cover Installation
Non-Powered Convenience Outlet
This type requires the field installation of a general-purpose
125-v 15A circuit powered from a source elsewhere in the
building. Observe national and local codes when selecting wire
size, fuse or breaker requirements, and disconnect switch size
and location. Route 125v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
18
in. (13 mm) under screw heads is
GFCI RECEPTACLE
NOT INCLUDED
GASKET
BASEPLATE FOR
GFCI RECEPTACLE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents