Siemens FDM275-O Technical Manual page 34

Radio manual call point
Hide thumbs Also See for FDM275-O:
Table of Contents

Advertisement

Maintenance / Repair
7
State of operational readiness after alarm activation
34 | 46
Building Technologies
Fire Safety
Radio manual call point FDM275-O with glass insert
The glass insert is covered by a foil. This foil holds the glass splinters together
when the glass insert is pushed in, making it possible to remove the glass insert
easily.
w The glass insert is broken and the internal alarm indicator flashes red with
flashing pattern number 6.
1. Remove the housing cover with the key.
a The switching unit is accessible.
2. Completely remove the broken glass insert (1) and dispose of it properly.
3. Place the new glass insert (6) between the following points:
Retainer (5)
Left and right stops (4)
Spring (2)
Triggering device (3)
a This pre-stresses the spring (2).
4. Install the housing cover on the back box.
Hook the top housing cover into the back box.
Snap the bottom housing cover into place in the back box.
5. If necessary, check the function of the manual call point. See the chapter
'Performance check'.
a The radio manual call point FDM275-O is ready for operation.
1
Figure 12: Replacing the glass insert
1
Broken glass insert
2
Spring
3
Triggering device
3
2
5
4
5
6
4
4
6
Stop
Retainer
New glass insert
A6V10425652_en--_f
2016-11-28