WIRING
Wiring LVCN‐40 Series to any LVCN‐414, LVCN‐210 & LVCN‐318 Series Sensor: LVCN‐40 Series and associated
level sensor require a 12 to 28 VDC power supply to operate. The maximum cable distance between LVCN‐40
Series and the sensor is 15' (4.5m). Follow the below steps to wire LVCN‐40 series with the sensor:
Sensor
Wiring identical for all series of LVCN‐414, LVCN‐210 & LVCN‐318 Series Sensors.
1. Connect the Red and Black wires of both LVCN‐40 Series and the sensor to the 12‐28 VDC power supply.
2. Connect the Green and White wires of LVCN‐40 Series to the corresponding Green and White wires of the
sensor.
3. Isolate the Green and White wires from active power to prevent a short of the configuration circuit.
Adding a Loop Powered Display
General Safety
Where personal safety or significant property damage can occur due to a spill, the application must
have a redundant backup safety system installed.
Wiring should always be done by a licensed electrician.
Supply voltage should never exceed 28 VDC.
Protect the sensor from electrical spikes by isolating the power.
Design a fail‐safe system for possible indicator and/or power failure.
Never use the sensor in environments classified as Hazardous.
Use only the Red, Black, Green and White wires.