6. Wiring Examples
Current output model HX71-MA, HX71-MA-NB (4 to 20 mA)
Voltage output models HX71-V1, HX71-V2, HX71-V1-NB, HX71-V2-
7. Relative Humidity Output Calculations
To calculate % Relative Humidity by measuring the current or voltage
output use the following formulas.
For 4-20 mA output:
% RH = (Current measured in milliamps – 4) ÷ 0.16
EXAMPLE:
For 0 to 1 Vdc output:
% RH = (Voltage measured in volts x 100)
EXAMPLE:
6
HX71 SERIES
RH Probe/Transmitter
HX71 CABLE
HX71 CABLE
Figure 5 - Current Transmitter Wiring Example
NB (0 to 1 Vdc or 0 to 5 Vdc)
HX71 CABLE
HX71 CABLE
Figure 6 - Voltage Transmitter Wiring Example
+
BLACK WIRE
RED WIRE
SHIELD WIRE
+
BLACK WIRE
RED WIRE
+
SHIELD WIRE
WHITE WIRE
BLACK WIRE
RED WIRE
SHIELD WIRE
+
WHITE WIRE
BLACK WIRE
RED WIRE
SHIELD WIRE
(11.04 mA – 4) ÷ 0.16 = 44% RH
0.44 Vdc x 100 = 44% RH