Point lists
3.4
Counters
Counters
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Counter with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter without Time)
Point In-
Name
dex
0
Wp+=
1
Wq+=
2
Wp-=
3
Wq-=
4
Wp(puls) =
5
Wq(puls) =
34
Description
Wp Forward (metered measurand derived from measured value)
Wq Forward (metered measurand derived from measured value)
Wp Reverse (metered measurand derived from measured value)
Wq Reverse (metered measurand derived from measured value)
Pulsed Energy Wp (active)(metering impulses at binary input)
Pulsed Energy Wq (reactive)(metering impulses at binary input)
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
32
Scaling(2
-1 of the unsigned long-
value corresponds to...)
32
2
-1 impulses
32
2
-1 impulses
32
2
-1 impulses
32
2
-1 impulses
32
2
-1 impulses
32
2
-1 impulses
C53000-L2040-A320-2