Page 1
Electronic Air Cleaner Model Number Model Number Model Number Model Number Model Number SST1000 SST1000 SST1000 SST1000 SST1000 SST1400 SST1400 SST1400 SST1400 SST1400 SST1600 SST1600 SST1600 SST1600 SST1600 SST2000 SST2000 SST2000 SST2000 SST2000 Please read and familiarize yourself with the contents of this manual before...
600 to 1200 cubic feet of air per minute (cfm.) Model SST1400 Model SST1400 Model SST1400 Model SST1400 is designed for heating or cooling blow- Model SST1400 ers delivering 1000 to 1600 cfm. Model SST1600 Model SST1600 Model SST1600 is designed for heating or cooling blow-...
HOW THE AIR CLEANER WORKS HOW THE AIR CLEANER WORKS HOW THE AIR CLEANER WORKS HOW THE AIR CLEANER WORKS HOW THE AIR CLEANER WORKS Dirt particles flowing through the ducts (Figure 1) first enters the pre-filters (A) where large particles (hair, lint, etc.) are trapped.
2. Allow the following clearances to permit removal of cells and pre-filters: (See Figures 4 and 5) Model SST1000 - 14 inches Model SST1400 - 15 inches Model SST1600 - 14 inches Model SST2000 - 15 inches For complete dimension data refer to Figure 5.
INSTALLATION INSTALLATION INSTALLATION INSTALLATION INSTALLATION REMOVE OLD FILTER AND DISCARD REMOVE OLD FILTER AND DISCARD REMOVE OLD FILTER AND DISCARD REMOVE OLD FILTER AND DISCARD REMOVE OLD FILTER AND DISCARD (Figure 12) (Figure 12) (Figure 12) (Figure 12) (Figure 12) NOTE: This filter may be mounted in the furnace compart- ment.
WIRING INSTRUCTIONS WIRING INSTRUCTIONS WIRING INSTRUCTIONS WIRING INSTRUCTIONS WIRING INSTRUCTIONS 7. With the cabinet installed, the air cleaner can now be wired to electrical input source. WARNING Installation of this unit must comply with local Installation of this unit must comply with local Installation of this unit must comply with local Installation of this unit must comply with local Installation of this unit must comply with local...
OPERATION OPERATION OPERATION OPERATION OPERATION 1. With the 120 VAC power turned on at the circuit breaker for the furnace, push the air cleaner ON-OFF switch to the “ON” position (Figure 20). 2. With the furnace blower running, the air cleaner will be operating.
1.0 Ma @ 6450 VDC (nom) Max. Ozone Output .05 ppm Temperature Rating 40 F to 125 F Support SST1400 SST1600 1000 - 1600 cfm 1000 - 2000 cfm .08 in. W.G. .12 in. W.G. (2) 9 lbs. each (2) 9 lbs. each 9 lbs.
BASIC SST SERVICE GUIDE BASIC SST SERVICE GUIDE BASIC SST SERVICE GUIDE BASIC SST SERVICE GUIDE BASIC SST SERVICE GUIDE This guide will cover most homeowner complaints. If, after checking the items listed, the unit still fails to operate properly, contact the nearest Authorized Service Center. SERVICE INDICATION SERVICE INDICATION SERVICE INDICATION...
TECHNICAL REPAIR GUIDE TECHNICAL REPAIR GUIDE TECHNICAL REPAIR GUIDE TECHNICAL REPAIR GUIDE TECHNICAL REPAIR GUIDE WARNING Do not attempt repair of this unit unless you are Do not attempt repair of this unit unless you are Do not attempt repair of this unit unless you are Do not attempt repair of this unit unless you are Do not attempt repair of this unit unless you are familiar with the necessary tools, equipment,...
Page 12
POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY POWER SUPPLY CHECKOUT PROCEDURE CHECKOUT PROCEDURE CHECKOUT PROCEDURE CHECKOUT PROCEDURE CHECKOUT PROCEDURE 1. Turn power switch to the “OFF” position and remove the power pack from cabinet. 2. If air flow switch is installed, locate air flow switch and remove power pack cover.
OZONE REDUCTION OZONE REDUCTION OZONE REDUCTION OZONE REDUCTION OZONE REDUCTION All electronic air cleaners typically produce a small amount of ozone that is within established limits. Some customers may notice an odor especially at high altitudes or low air flow rates. This power supply has a “hairpin”...
A regular washing schedule is necessary to ensure proper efficiency. A thorough washing once every month will be adequate for most installations. More or Less Year FEB MAR APR MAY JUN 20___ 20___ 20___ 20___ 20___ 20___ 20___ 20___ 20___ 20___ 20___ 20___...