Installing the air conditioner
• Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC66 / CENELEC H07RN-F)
NOTE
• This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal
to Ssc (*2) at the interface point between the user's supply and the public system. It is the responsibility of the
installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).
[Ssc (*2)]
• Please use rated wires or products (with heat resistance over 105 °C) of all the wires and the switches or fuses in
the cabinet panel. (Retailer and installer is responsible for the use of parts that does not meet the wire standards
CAUTION
or capacity requirements)
• Make sure that wires doesn't make any sparks around the auxiliary power switch or installed in a place with
high temperature. (If the ambient temperature is high, allowable current of the wire will decrease and current
reduction factor will occur.)
• Please install the auxiliary power switch in a dry place and install panel board or electrical component box.
• Please install circuit breaker in the panel board.
• When connecting the main power, press the wire to the terminal to secure connection.
• Selecting crimp-style ring terminal
Thickness of the wire (mm
Connecting the power terminal
f Connect the cables to the terminal board with solderless ring terminals.
f
f Only sue the certified and rated cables and make sure to firmly connect them without applying any external force to the
f
terminal.
f Connect with a driver and a wrench that are able to apply the rated torque to the screws.
f
f Connect the terminal screws according to the rated tightening torque. If the terminal is loose, fire can occur due to arc
f
heat generation and if the terminal is too tight, terminal board could get damaged.
Tightening torque for terminal (kgf∙cm)
PAC MIRAGE Saudi_IBIM_EN_CS6_DB68-04872A-05.indd 49
MODEL
AF55JV3MAEEXMG
AF55JV1MAEEXMG
Silver solder
)
2
2.5
4
6
10
Screw
ENGLISH-49
Ssc[MVA]
B (mm)
Less than 9.5
Less than 9.5
Less than 9.5
Less than 15
M3
M3.5
M4
5.0 ~ 7.5
8.0 ~ 12.0
12 ~ 18
0.944
0.819
d2 (mm)
More than 4.5
More than 4.5
More than 4.5
More than 8.4
M5
M6
20 ~ 30
25 ~ 37.5