Fig. 59 — Conduit into Control Box (Size 16)
Fig. 60 — Conduit into Single Point Box (Size 16)
Fig. 61 — Mounting Position for Field Disconnects
(over 100A) (Size 16)
Fig. 62 — Mounting Position for Field Disconnects
(up to 100A) (Size 16)
Field power wires are connected to the unit at line-side pres-
sure lugs at the main terminal block (TB1) or at factory-
installed option non-fused disconnect switch. Max wire size is
#2 AWG (copper only). See Fig. 63.
Units Without Disconnect Option
Units With Disconnect Option
L1
2
L2
4
L3
6
Disconnect factory test leads; discard.
Fig. 63 — Power Wiring Connections (Size 16)
NOTE: TEST LEADS - Unit may be equipped with short leads
(pigtails) on the field line connection points off the optional dis-
connect switch. These leads are for factory run-test purposes only;
remove and discard before connecting field power wires to unit
connection points. Make field power connections directly to line
connection pressure lugs only.
43
TB1
11
12
13
Disconnect
per
NEC
L1
L2
L3
208/230-3-60
460-3-60
575-3-60
1
Optional
Disconnect
3
Switch
5
Factory
Wiring