Custom Code Setting; Function Setting - Fujitsu Airstage ABUA30RLAV Installation Manual

Indoor unit, ceiling type
Table of Contents

Advertisement

Rotary Switch
Address
Setting
Refriger-
REF AD SW
× 10
ant circuit
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
.
.
.
.
.
.
99
9
Do no t set the indoor unit address (IU AD SW) at 64 to 99. It may result in failure.
(3) Remote controller address
Rotary switch (RC AD SW) .... Factory setting "0"
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting
Setting range
Remote controller
0 to 15
address
Example If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
Remote
controller
RC AD SW
0
1
Address
0
1
RC AD SW
8
9
Address
8
9
] 1

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up. (Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Fig. B
Confusion
Indoor unit
Remote
controller
Custom code setting for indoor unit
Set the DIP SW SET 3 SW1, SW2, referring to the Table B.
ON
OFF
SW SW SW SW
1
2
En-13
Table A
Rotary Switch
Address
IU AD SW
Indoor unit
× 1
× 10
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
0
0
10
1
1
11
1
2
12
1
.
.
.
.
.
.
.
.
.
9
63
6
Type of switch
Setting
example
0
RC AD
Indoor unit
Indoor unit
RC AD SW
RC AD SW
1
2
3
2
3
4
5
2
3
4
5
A
B
C
D
10
11
12
13
Code change
A
B
C
D
A
B
C
D
Dip switch
"SET 3"
3
4
Setting
DIP SW SET 3 SW1
× 1
DIP SW SET 3 SW2
0
1
2
FUNCTION SETTI
1

7.3. Function setting

3
4
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
5
(The remote controller is optional equipment)
6
• Refer to the wired or wireless remote controller manual for detailed setting information.
7
(Set IU AD, REF AD SW to 0)
8
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
9
• Turn the power of the indoor unit ON before starting the setting.
0
1
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
2
tight test and vacuuming have been conducted before turning on the power.
.
.
* Also check again to make sure no wiring mistakes were made before turning on the
.
power.
3
Function details
Function
Function
number
Filter
indicator
interval
Filter
indicator
action
Horizontal
swing
airfl ow
direction
Cool air
tem-
6
7
perature
trigger
6
7
E
F
14
15
Heat air
tem-
perature
trigger
Auto
restart
External
control
Error re-
port target
Table B
Custom code
A (Factory setting)
OFF
OFF
Setting number Default
00
Default
11
01
Longer
02
Shorter
00
Enable
01
Disable
13
Display only on
02
central remote
controller
00
Default
24
01
Left half
02
Right half
00
Default
30
01
Adjust (1)
02
Adjust (2)
00
Default
01
Adjust (1)
31
02
Adjust (2)
03
Adjust (3)
00
Enable
40
01
Disable
00
Start/Stop
Emergency
46
01
stop
02
Forced stop
00
All
47
Display only on
01
central remote
controller
B
C
D
ON
OFF
ON
OFF
ON
ON
Details
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too
early, change to setting 01. If the
notifi cation is too late, change to
setting 02.
Enable or disable the fi lter indicator.
Setting 02 is for use with a central
remote controller.
Adjust the horizontal swing airfl ow
direction.
(For horizontal swing equipped
models)
Adjust the cool air trigger tempera-
ture. To lower the trigger tempera-
ture, use setting 01. To raise the
trigger temperature, use setting 02.
Adjust the heat air trigger temperature.
To lower the trigger temperature by
11 degrees F (6 degrees C), use setting
01. To lower the trigger temperature by
7 degrees F (4 degrees C), use setting
02. To raise the trigger temperature,
use setting 03.
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency
function such as for power failure
etc.
Do not start and stop the indoor
unit by this function in normal
operation.
Be sure to operate by the control
unit, converter or external input
device.
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all
refrigerant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
Change the target for reporting er-
rors. Errors can either be reported in
all locations, or only on the central
remote controller.