Table 14 — Open System Wiring Specifications and Recommended Vendors
Wire Type
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated.
See MS/TP Installation Guide for specifications.
MS/TP
Network (RS-485)
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated.
See MS/TP Installation Guide for specifications.
Rnet
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
LEGEND
AWG
— American Wire Gage
CL2P
— Class 2 Plenum Cable
CMP
— Communications Plenum Rated
FEP
— Fluorinated Ethylene Polymer
TC
— Tinned Copper
© 2013 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300110-01
Fig. 63 — BT485 Terminator Installation
WIRING SPECIFICATIONS
Description
Printed in U.S.A.
RECOMMENDED VENDORS AND PART NUMBERS
Connect Air
International
W221P-22227
W241P-2000F
W184C-2099BLB
Form 30XA-19SI Rev. A
Pg 162
Contractors
Belden
RMCORP
Wire and Cable
25160PV
CLP0520LC
82841
25120-OR
6302UE
21450
CLP0442
2-2020
Replaces: 30XA-18SI