NOTE: All charging specifications are at nominal conditions: ambient temperature of 77 °F (25 °C), 120 VAC, 60 Hz input, unless
otherwise specified.
Charger Specifications
Charging method
Without a battery temperature sensor
With a battery temperature sensor (included)
Output current (maximum)
Output voltage
Output voltage range
Equalization cycle
Optimal charging efficiency
AC input power factor (at full charge rate)
AC input current
AC input voltage
AC input voltage range
Dead battery charge voltage
Supported AC input types
72
Three-stage charge (Bulk, Absorption, Float)
Two-stage charge (Bulk, Absorption)
The default charging method is three-stage.
Three settings with the following temperature values:
Cool 50 °F (10 °C) / Warm 77 °F (25 °C) / Hot 104 °F (40 °C)
The default setting is Warm and it can only be changed by the factory, a dealer, or a service centre.
The temperature compensation coefficients on a
12-volt battery are as follows:
Flooded: 27 mV × (25 °C – BTS °C)
Gel: 27 mV × (25 °C – BTS °C)
AGM: 21 mV × (25 °C – BTS °C)
100 ADC
12 VDC
5–16 VDC
Automatic, Manual by anbus SCP
> 85%
> 0.98
24A max. (including pass-thru)
120 VAC
85–140 VAC
> 5 VDC
Single input (up to 30 amps)
Specifications
The temperature compensation coefficients on a
24-volt battery are as follows:
Flooded: 54 mV × (25 °C – BTS °C)
Gel: 54 mV × (25 °C – BTS °C)
AGM: 42 mV × (25 °C – BTS °C)
150 ADC
12 VDC
5–16 VDC
Automatic, Manual by anbus SCP
> 85%
> 0.95
24A max. (including pass-thru)
120 VAC
85–140 VAC
> 5 VDC
Split phase (up to 30 amps per line)
Dual input (up to 30 amps per line)