Step 14 Optional: Extending The Power Cable - Samsung AC RN DKG Series Installation Manual

Hide thumbs Also See for AC RN DKG Series:
Table of Contents

Advertisement

Step 14 Optional: Extending the
power cable
1 Prepare the following tools.
Tools
Crimping pliers
MH-14
Connection sleeve
20xØ6.5
(mm)
(HxOD)
Width 19
Insulation tape
Contraction tube
70xØ8.0
(mm)
(LxOD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
Peel off 20 mm of cable shields from the pre-
installed tube.
CAUTION
For information about the power cable
specifications for indoor and outdoor units, refer
to the installation manual.
After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
Power cable
20
Pre-installed tube for the power cable
(Unit: mm)
20
Spec
Shape
mm
20
20
60
120
180
(Unit: mm)
3 Insert both sides of core wire of the power cable into
the connection sleeve.
Method 1: Push the core wire into the sleeve from
both sides.
Method 2: Twist the wire cores together and push
it into the sleeve.
Method 1
Connection sleeve
4 Using a crimping tool, compress the two points and
flip it over and compress another two points in the
same location.
The compression dimension should be 8.0.
After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Method 1
Compress it 4 times.
5 mm
5 Wrap it with the insulation tape twice or more and
position your contraction tube in the middle of the
insulation tape.
Three or more layers of insulation are required.
Method 1
Insulation tape
40 mm
Method 2
Connection sleeve
Compression
dimension
Method 2
Compress it 4 times.
5 mm
Method 2
Insulation tape
35 mm
21
English

Advertisement

Table of Contents
loading