1MRK 511 244-UUS A
Section 3
3.1

DNP3 device profile

The following table provides a device profile document in the standard format defined in the DNP3
Subset Definitions Document. While it is referred to in the DNP3 Subset Definitions as a document,
it is in fact a table, and only a component of a total interoperability guide. The table, in
combination with the Implementation table and the point list tables, provides a complete
configuration/interoperability guide for communicating with a device.
Table 7:
Device profile document
DNP3 device profile document
Vendor name:
Device name:
Highest DNP level supported:
For requests:
For responses:
Notable objects, functions and/or qualifiers supported in addition to the highest DNP levels supported (the complete list is
described in the attached table):
For static (non-change event) object requests, request qualifier codes 07 and 08 (limited quantity) and 17 and 28 (index) are
supported. Static object requests sent with qualifiers 07 or 08 are responded with qualifiers 00 or 01.
16-bit, 32-bit and Floating point analog change events with time may be requested.
Floating point analog output status and output block objects 40 and 41 are not supported.
Sequential file transfer, object 70, variations 2 through 7, are not supported.
Octet string and string event objects 110 and 111 are not supported.
Virtual terminal output and event objects 112 and 113 are not supported.
Device attribute object 0 is not supported.
Data set objects 85-88 are not supported.
Maximum data link frame size (octets):
Transmitted:
Received:
Maximum data link retries:
None
Fixed
Configurable (0...65535)
(DLinkRetries for each channel)
Requires data link layer confirmation:
Never
Always
Sometimes
Configurable as: only when reporting event data
(DLinkConfirm for each channel)
Requires application layer confirmation:
Never
Table continues on next page
DNP, 650 series
Point list manual

DNP3 protocol implementation

Level +
Level +
292
292
© Copyright 2011 ABB. All rights reserved
ABB AB
650 series IED
Device function:
Master
Slave
Maximum application fragment size (octets):
Transmitted:
Configurable up to 2048
(ApLayMaxTxSize for each master session)
Received:
Configurable up to 2048
(ApLayMaxRxSize for each Master session)
Maximum application layer retries:
None
Configurable
Section 3
DNP3 protocol implementation
GUID-701D9FB2-8EE8-46D0-A5A1-001428923A2F v2