ELECTRICAL CONNECTIONS

It is advisable to leave the control box off the sub-base while
completing the electrical connections to the burner.
1) Wire access hole (Use BX electrical connector)
2) Earth ground conductor terminal (GREEN WIRE)
3) Hot conductor terminal (BLACK WIRE)
4) Neutral conductor terminal (WHITE WIRE)
5) Strain relief clamp
WARNING:
The hot (black) wire must be connected to the L terminal and the
neutral (white) wire must be connected to the N terminal or the
primary safety control will be damaged.
Do not connect wither wire to the terminal marked
Using the appropriate diagram below, make electrical connections
to burner. All wiring must be done in accordance with existing electrical codes, both national and local.
When all electrical connections have been made, the control box may be put back in place on the sub-base.
WARNING: DO NOT activate burner until proper oil line connections have been made, or failure of the pump shaft
seal may occur.
APPLICATION FIELD WIRING
NOTE: Terminal 4 is to be used to activate a remote safety lockout circuit only. A 120V AC source is supplied to Terminal
4 upon lockout. The maximum allowable current draw for this circuit is 1 AMP.
IMPORTANT: if a neutral or ground lead is attached to Terminal 4, the control box will be damaged should lockout occur.
2902453
EARTH
GROUND
N
1
2
3
SAFETY
VALVE
SOLENOID
Black
VALVE
.
120V
.
AC
FUSE 15A
LINE SAFETY
SWITCH
OPERATING
LIMIT SWITCH
SAFETY
LIMIT SWITCH
L
4
5
6
7
M
~
CAPACITOR
MOTOR
5
S7436
DIRECT LINE
VOLTAGE
8
9
FACTORY WIRED
SUB-BASE
20101923
GB