Haier HCFU-42CF03 Service Manual page 51

Commercial air conditioning
Hide thumbs Also See for HCFU-42CF03:
Table of Contents

Advertisement

CN13
input signal, wiring port of remote receiver board: RECEIVE BOARD 1. power supply 5VDC,
2. power supply 0VDC, 3. remote signal, 4. signal output of running lamp 0VDC, 5. signal output of timer
lamp 0VDC,6. signal output of power lamp 0VDC, 7. signal output of water pump running lamp 0VDC
CN14
control external load, auto elevating function
elevating direction control 0VDC, 3. output of elevating power control 0VDC, 4. power supply 12VDC
CN15
input signal, detecting water level of float switch
that level exceeds the limitation .If float switch cuts off or occurs other failure, LED1 will flash 10 times.
CN16
input control, wiring port of central controller: REMOTE 1 RS485-B 2 RS485-A
CN17
output signal, output signal of failure alarm, control external load, 12V/ALM 1. control output
0VDC, 2. power supply 12VDC
CN18
output signal (no use)
CN19
control external load, swing 1 1 16VDC 2 0VDC 3 0VDC 4 0VDC 5 0VDC.
CN20
control external load, swing 2 1 16VDC 2 0VDC 3 0VDC 4 0VDC 5 0VDC.
CN21
input signal, spring switch, CHECK 1 input signal of earthing, 2. power supply 0VDC
CN22
short circuit means selecting single split communication type.
CN23
short circuit means selecting multi split communication type.
51
Commercial Air Conditioner
Model: HCFU-42CF03
1. signal of door switch close, 2. output of
1-3 short circuit is normal, cut off shows