Group Number Setting; Test Run; Cool & Heat Selector - LG MULTI V S ARUB060GSS4 Installation Manual

Hide thumbs Also See for MULTI V S ARUB060GSS4:
Table of Contents

Advertisement

28
Mode
Function
Option
Content Display1
Content
Display2
Content
Cool & Heat
oFF op1~
Selected
Selector
op2
the option
Static
oFF op1~
Selected
pressure
op3
the option
compensation
Night low
oFF op1~o
Selected
noise
p12
the option
ODU
-
address
Snow
oFF op1~
Selected
removal &
op3
the option
rapid defrost
Target
oFF op1~
Selected
pressure
op3
the option
adjusting
* Functions save in EEPROM will be kept continuously, though the
system power was reset.
* DIP switch 3 can be OFF except when installing the only 4 series
indoor units (named ARNU***4).

Group Number setting

Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is
OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal
should be connected to central control of Outdoor Unit with care for
their polarity (A-A, B-B).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID
from 0 to F for this purpose.
Outdoor Units (Main PCB)
ODU.B
ODU.A
IDU.B
IDU.A
CEN.B
CEN.A
B(D)
Example) Group number setting
1 F
Group Indoor unit
st
1
number indicate the group number
2nd number point out indoor unit number
Group recognizing the central controller
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)
Value
Action
Remarks
Display3 Content Display4 Implement Display5
Change
Save in
-
-
the set
Blank
EEPROM
value
Change
Save in
-
-
the set
Blank
EEPROM
value
Change
Save in
-
-
the set
Blank
EEPROM
value
set
Change
Save in
-
0~255
the
the set
Blank
EEPROM
value
value
Change
Save in
-
-
the set
Blank
EEPROM
value
Change
Save in
-
-
the set
Blank
EEPROM
value
DRY1
DRY2
GND
12 V
A(C)
WARNING
!
• Valve address and central control address of its corresponding indoor
unit should be set identical in manual addressing.
EX)
Valve (04)
Valve (03)
HR unit
Valve (02)
Valve (01)

TEST RUN

Cool & Heat selector
Mode setting method
Service PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn1" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF", "op1", "op2" Push the '●' button
Cool & Heat Selection mode is set
Function setting
Switch control
Switch(TOP)
Switch(Bottom)
oFF
Right
Left
Not operate
Right
Right
Not operate
Left
-
Not operate
Right side
Left side
Switch (TOP)
Switch (Bottom)
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, first install a Cool & Heat selector.
Indoor unit (04)
Indoor unit (03)
Indoor unit (02)
Indoor unit (01)
Central control address
Function
op1(mode)
op2(mode)
Cooling
Cooling
Heating
Heating
Fan mode
Off