Automatic Addressing - LG MULTI V S ARUB060GSS4 Installation Manual

Hide thumbs Also See for MULTI V S ARUB060GSS4:
Table of Contents

Advertisement

3 SW01M/SW03M/SW04M (DIP S/W and tact S/W for
manual valve addressing)
1) Normal setting (Non-Zoning setting)
- Set the address of the valve of the HR unit to the central control
address of the connected indoor unit.
- SW01M: selection of the valve to address
SW03M: increase in the digit of 10 of valve address
SW04M: increase in the last digit of valve address
- Prerequisite for manual valve addressing : central control address
of each indoor unit must be preset differently at its wired remote
control.
S/W No.
No.1
Manual addressing of valve #1
No.2
Manual addressing of valve #2
No.3
Manual addressing of valve #3
SW01M
No.4
Manual addressing of valve #4
Increase in the digit of 10 of valve
SW03M
SW03M
address
Increase in the last digit of valve
SW04M
SW04M
address
2) Zoning setting
- Set the address of the valve of the HR unit to the central control
address of the connected indoor unit.
- SW01M : selection of the valve to address
SW03M : increase in the digit of 10 of valve address
SW04M : increase in the last digit of valve address
SW05M : Rotary S/W
- Prerequisite for manual valve addressing : central control address
of each indoor unit must be preset differently at its wired remote
control.
S/W No.
No.1
No.2
No.3
SW01M
No.4
SW03M
SW03M
SW04M
SW04M
SW05M
SW05M
Setup
Setup
Manual addressing of valve #1
Manual addressing of valve #2
Manual addressing of valve #3
Manual addressing of valve #4
Increase in the digit of 10 of valve
address
Increase in the last digit of valve
address
Manual addressing of zoning
indoor units

Automatic Addressing

The address of indoor units would be set by Automatic Addressing
- Wait for 3 minutes after supplying power.
(Master and Slave outdoor units, indoor units)
- Press RED button of the outdoor units for 5 seconds. (SW01C)
- A "88" is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on
numbers of connected indoor units
- Numbers of connected indoor units whose addressing is completed are
indicated for 30 seconds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated
on the wired remote control display window. (CH01, CH02,
CH03, ......, CH06 : Indicated as numbers of connected indoor units)
[Heat Recovery (SERVICE PCB)]
7-Segment
SW01C( :confirm)
SW02C( :backward)
SW03C( :forward)
CAUTION
!
• In replacement of the indoor unit PCB, always perform Automatic
addressing setting again (At that time, please check about using
Independent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error
occur.
• Automatic Addressing is only possible on the master Unit.
• Automatic Addressing has to be performed after 3 minutes to
improve communication.
The Procedure of Automatic Addressing
Power On
Waiting 3 minutes
Press RED Button for
5 seconds (SW01C)
Automatic addressing start
7-segment LED
= 88
Don't press RED Button
(SW01C)
• Automatic addressing setting end
Numbers of indoor unit connection set whose
addressing is completed are indicated for 30seconds
Waiting about 2~7 minutes
on 7-segment LED after completing setting
NO
7-segment LED
= 88
YES
Indoor address number is displayed on wired remote control or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units
OK
and Automatic addressing is completed normally.
25
SW01D(reset)
SW04C(x:cancel)
DIP-SWITCH
Check the connections
of communication cable