HEAT SECTION − 036/060 UNITS
(060 Shown)
FIGURE 6
HEAT SECTION − 120, 240, & 288 UNITS
BURNERS
FIGURE 7
5− Turn on the electrical power and the gas supply to the
unit. Follow the operating instructions attached to the
unit and use the inspection port in the access panel
to check the flame.
BURNER
SUPPORT CAP
SCREWS SECURING
BURNER TO BURNER
SUPPORT
BURNER
SUPPORT
Page 6
!
WARNING
Electric shock hazard and danger of
explosion. Can cause injury, death or
product or property damage. Turn off
gas and electrical power to unit before
performing
servicing operations on the unit. Follow
lighting instructions attached to unit
when putting unit back into operation
and after service or maintenance.

Combustion Air Inducer

A combustion air proving switch checks combustion air
inducer operation before allowing power to the gas
controller. Gas controller will not operate if inducer is
obstructed.
Under normal operating conditions, the combustion air
blower wheel should be checked and cleaned prior to the
heating season. However, it should be examined
periodically during the heating season to establish an ideal
cleaning schedule. With power supply disconnected, the
condition of the blower wheel can be determined by
looking through the vent opening.

Cleaning Combustion Air Inducer

1− Shut off power supply and gas to unit.
2− Disconnect
pressure
combustion air inducer port.
3− Remove
and
retain
combustion air inducer to flue box. Remove and
retain two screws from bracket supporting vent
connector. See figure 3 or 4.
4− Clean blower wheel blades with a small brush and
wipe off any dust from housing. Clean accumulated
dust from front of flue box cover.
5− Return combustion air blower motor and vent
connector to original location and secure with
retained screws. It is recommended that the
combustion air inducer gasket be replaced during
reassembly.
6− Clean combustion air inlet louvers on heat access
panel using a small brush.
any
maintenance
switch
air
tubing
from
four
screws
securing
or

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sga060Sga120Sga240Sgb288