7 MAINTENANCE AND INSPECTION
7.2 Daily Inspection
Daily inspection items are as follows.
Number
Inspection Item
1
Module mounting status
Loose
terminal
screws
Connection
Proximate
2
status
solderless
terminals
Loose
connectors
7.3 Periodic Inspection
Inspection items to be checked once or twice in six months or one year are as follows.
The following inspection should also be performed when equipment has been moved
or modified or the wiring changed.
Number
Inspection Item
Ambient
temperature
Surround-
ing
1
environ-
Ambient
ment
humidity
Atmos-
phere
Power supply voltage
2
check
Looseness
Mounting
3
Dirt, foreign
status
matter
Loose
terminal
screws
Connection
Proximate
4
status
solderless
terminals
Loose
connectors
7 - 2
Inspection Method
Check for loose mounting
screws and disconnected
Securely mounted
cover
Retighten screws with
Not loose
screwdriver
Visual check
Proper intervals
Visual check
Not loose
Inspection Method
Display
section
Make measurement with
Other
portions
thermometer or
hygrometer
10 to 90%RH
Measure corrosive gas
No corrosive gas
24VDC
Measure voltage across
20.4DC to 26.4V
terminals
Move module
Should be mounted firmly Retighten screws
No dirt, foreign matter
Visual check
sticking
Retighten screws with
Not loose
screwdriver
Visual check
Proper intervals
Visual check
Not loose
MELSEC-GOT
Criterion
Action
Retighten screws
Retighten terminal
screws
Correct
Retighten connector
fixing screws
Criterion
Action
C
0 to 40
For use in enclosure,
C
0 to 55
temperature inside
enclosure is ambient
temperature
Change supply power
Remove, clean
Retighten terminal
screws
Correct
Retighten connector
fixing screws
7
7 - 2