Daily Inspection; Periodic Inspection - Mitsubishi A950GOT User Manual

Table of Contents

Advertisement

7.2 Daily Inspection

Daily inspection items are as follows.
Number
Inspection Item
1
Module mounting status
Loose termi-
nal screws
Proximate
Connection
2
solderless ter-
status
minals
Loose con-
nectors

7.3 Periodic Inspection

Inspection items to be checked once or twice in six months or one year are as follows.
The following inspection should also be performed when equipment has been moved or modified or the wir-
ing changed.
Number
Inspection Item
Ambient tem-
perature
Surrounding
1
environment
Ambient
humidity
Atmosphere
2
Power supply voltage check
Looseness
Mounting sta-
3
Dirt, foreign
tus
matter
Loose termi-
nal screws
Proximate
Connection
4
solderless ter-
status
minals
Loose con-
nectors
Inspection Method
Check for loose mounting
screws and disconnected
cover
Retighten screws with screw-
driver
Visual check
Visual check
Inspection Method
Make measurement with ther-
mometer or hygrometer
Measure corrosive gas
24VDC
Measure voltage across termi-
nals
Move module
Visual check
Retighten screws with screw-
driver
Visual check
Visual check
Get other manuals https://www.bkmanuals.com
Criterion
Securely mounted
Retighten screws
Not loose
Retighten terminal screws
Proper intervals
Correct
Retighten connector fixing
Not loose
screws
Criterion
Display sec-
0 to 40
tion
For use in enclosure, tempera-
Other portions
0 to 55
ture inside enclosure is ambi-
ent temperature
10 to 90%RH
No corrosive gas
20.4DC to 26.4V
Change supply power
Should be mounted firmly
Retighten screws
No dirt, foreign matter sticking
Remove, clean
Not loose
Retighten terminal screws
Proper intervals
Correct
Retighten connector fixing
Not loose
screws
7.2 Daily Inspection
1
Action
2
3
4
Action
5
6
7
8
7 - 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

A951gotA953gotA956got

Table of Contents