Carrier Accessory Kits
There are specific accessory kits sold for various field installed
accessories.
These kits vary based on model, size, voltage,
manufacture date, and duct orientation. Some of these kits include
Economizer, Power Exhaust, and Electric Heat.
Controls Quick Set- -Up section for configuration and more
information on these accessories.
Two- - Position Damper
The two-position outdoor air damper accessory usage depends on
model size and return duct orientation. This accessory wires
directly into the low voltage circuit for the indoor fan control. No
other control configuration is needed.
Indoor Air Quality
The indoor air quality (IAQ) sensor (part no. 33ZCSENCO2) is a
field-installed accessory which measures CO
When installing this sensor, an ECB board must be installed and
the unit must be configured for IAQ use by setting
Configuration→AIR.Q→IA.CF to a value of 1, 2, or 3. See the
Indoor Air Quality section for more information.
TB- -2
. . . . . . . . . .
4- -20mA Input
TB- -3
. . . . . . . . . .
Sensor Common
TB- -R
. . . . . . . . .
24vac Output
TB- -C
. . . . . . . . .
Common (GND)
Outdoor Air Quality
The outdoor air quality (OAQ) sensor is a field-installed accessory
that measures CO
levels in the air. When installing this sensor, an
2
ECB board must be installed and the unit must be configured for
OAQ use by setting Configuration→AIR.Q→OA.CF to a value
of 1 or 2. See the Indoor Air Quality section for more information.
TB- -2
. . . . . . . . . .
4- -20mA Input
TB- -3
. . . . . . . . . .
Sensor Common
TB- -R
. . . . . . . . .
24vac Output
TB- -C
. . . . . . . . .
Common (GND)
Smoke Detectors
The smoke detectors are field-installed accessories. These detectors
can
detect
smoke
in
either
CRSMKDET003A00) or supply and return air (part no.
CRSMKSUP002A00). When installing either detector, the unit
must
be
configured
for
Configuration→UNIT→FS.SW to normally open (1) or normally
closed (2).
TB- -Fire Shutdown- -1
. . . . . . . . . . . . .
TB- -Fire Shutdown- -2
. . . . . . . . . . .
TB- -R
. . . . . . . . .
24vac Output
TB- -C
. . . . . . . . .
Common (GND)
NOTE: When a Humidi-Mizer™ system is installed, the inputs to
the fire shutdown are moved to the control harness. See the Third
Party Control section for more information.
Filter Status
The filter status accessory (part no. CRSTATUS002B00) is a
field-installed accessory. This accessory detects plugged filters.
When installing this accessory, the unit must be configured for
filter status by setting Configuration→UNIT→FL.SW to
normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.
Filter status wires are pre- -run in the unit harness and located near
the switch installation location.
installation instructions for more information.
Refer to the
levels in the air.
2
the
return
air
(part
no.
fire
shutdown
by
setting
Dry Contact Source
Discrete Input to Board
Refer to the Filter Accessory
Fan Status
The fan status accessory (part no. CRSTATUS003B00) is a
field-installed accessory. This accessory detects when the indoor
fan is blowing air. When installing this accessory, the unit must be
configured
for
fan
Configuration→UNIT→FN.SW to normally open (1) or
normally closed (2). Normally open (1) is the preferred
configuration.
Fan status wires are pre- -run in the unit harness and located near the
switch installation location. Refer to the Fan Accessory installation
instructions for more information.
NOTE: The fan status terminals on TB1 are NOT to be used.
Enthalpy Sensors
The enthalpy accessories (part no. CRENTSNG002A00 and
CRENTDIF002A00) are field-installed accessories. The first
accessory (outdoor air only) determines when the enthalpy is low
relative to a fixed reference. Adding the second accessory (return
air) compares the enthalpy between the outdoor and return
airstreams. In each case, the enthalpy 4 to 20 mA signals are
converted to a switch output which is read by the ECB. When
installing this accessory, the unit must be configured for
enthalpy-based
control
Configuration→ECON→EN.SW to normally open (1). See Fig.
29 and 30 for wiring details.
Normal status is an active switch which tells the control that
enthalpy is LOW. The actual switch terminal LOW is normally
closed. Refer to the Enthalpy Kit installation instructions for more
information on the installation.
Return/Supply Air Temperature Sensor
The temperature sensor (part no. 33ZCSENSAT) is a field-installed
accessory which may be installed on the common return air duct
and/or the common supply air duct near the unit. The duct return
air temperature (RAT) may be selected for display only if the space
temperature offset (SPTO) is not used. When installing the sensor,
the
unit
must
be
Configuration→UNIT→RAT.S to YES. The duct supply air
temperature (SAT) may be used to replace the SAT sensor that is
internal to the unit. A supply duct SAT measurement is valid for
heating mode display while the factory-standard internal SAT is
not valid for heating due to its location upstream of the heating
section. When installing the supply duct SAT, the unit must be
configured by setting Configuration→UNIT→SAT.H to ENBL.
A SAT sensor in the supply duct is the preferred configuration for
systems with Carrier variable volume and temperature (VVT®)
accessory controls.
Space Humidistat
The Space Humidistat (part no. - -- -HL- -- -38MG- -029) is a wall
mounted device with an adjustable setpoint to control humidity
levels. The humidistat input is provided on the field connection
terminal board. The Space Humidity Switch configuration,
Configuration→UNIT→RH.SW, identifies the normally open or
normally closed status of this input at LOW humidity.
TB- -HUMIDISTAT1
. . . . . . . . . . . .
TB- -HUMIDISTAT2
. . . . . . .
NOTE: The humidistat terminals are only in use when the unit is
equipped with the Humidi- -MiZer factory option.
85
status
by
setting
by
setting
configured
by
setting
Discrete Input to Board
24 VAC Dry Contact Source