Ceiling Dimension And Hanging Bolt Location - LG ARNU18GTQD4 Installation Manual

Ceiling cassette, 4way
Hide thumbs Also See for ARNU18GTQD4:
Table of Contents

Advertisement

Installation

Ceiling dimension and hanging bolt location

• The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.
Ceiling
TQ/TR Chassis
585~660(Ceiling opening)
517
!
CAUTION
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level
gauge.
• During the installation, care should be taken
not to damage electric wires.
NOTICE
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is
generated.
4. Avoid place where noxious gas is
generated.
5. Avoid places near high frequency
generators.
12
Indoor Unit
Level gauge
570
461
Unit:mm
TM/TN/TP Chassis
875 (Ceiling opening)
787 (Hanging bolt)
840 Unit size
• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain
direction after considering the direction of drain hose.
• Drill the hole for anchor bolt on the wall.
Air conditioner
Take enough
distance
Ceiling board
Unit:mm
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents