Installation

Installation
Read completely, then follow step by step.

Selection of the best location

• If the temperature might rise above 30 ℃ or the humidity might rise above RH 80 %, attach the
Dew-Protective kit or use another insulation to the indoor body.
h Dew Protective kit is sold separately.
Use glass wool material or polyethylene foam and make sure at least 10 mm thick.
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must have the maintenance space.
Ceiling Board
500 or
more
!
CAUTION
In case that the unit is installed near the sea, the installation parts may be corroded by salt.
The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
h Please use an annexed sheet or the corrugated
cardboard on the bottom of packing as
installation sheet.
Annexed sheet
10
Indoor Unit
Ceiling
Or
Packing corrugated
cardboard on the
bottom
Ceiling Board
500 or
more
Floor
h When using the bottom sheet, please use it
after separating the installation sheet from
packing of the product floor by using a knife etc
as a picture below.
Unit:mm

Hide quick links: